IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx QPS 14.0003X issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2014-04-15 Page 1 of 3


    
Applicant:
Hebeler Corporation
2000 Military Road
Tonawanda, NY 14150
United States of America


 
Equipment:Model 24293A -000 B9G1 CAB; Serial Number 24293A / 02/2014-B9G1
Optional accessory:


 
Type of Protection:Ex d d [ia] e ia [ib] ib mb nA nC IIB+H2 T3 Gc


 
Marking:

Model No. 24293A -000 B9G1 CAB

Serial No. 24293A / 02/2014 - B9G1

Ex d d [ia] e ia [ib] ib mb nA nC IIB+H2 T3 Gc 

Tamb = 0C to +50C

IECEx QPS 14.0003X

 

 
Approved for issue on behalf of the IECEx
Certification Body:
Alfonso Mattucci

 
Position:QA Engineer


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
QPS
Evaluation Services Inc.
81 Kelfield St
Unit 8
Toronto, Ontario M9W 5A3
Canada


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx QPS 14.0003X
 
Date of Issue:2014-04-15Issue No.: 0
 
Page 2 of 3
 
 Manufacturer:
Hebeler Corporation
2000 Military Road
Tonawanda, NY 14150
United States of America


 
 Additional Manufacturing location(s):

 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2000
Edition: 3.1
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
CA/QPS/ExTR14.0002/00


Quality Assessment Report:

US/UL/QAR11.0007/01


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx QPS 14.0003X
 
Date of Issue:2014-04-15Issue No.: 0
 
Page 3 of 3
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

Model 24293A -000, B9G1 CAB.  Electrical Ratings 460V, 3-Ph, 60Hz / 230V, 1-Ph, 60Hz / 110V, 1-Ph, 60Hz / 24Vdc

The B9G1 Collector CAB Assembly is component part of a large system and directly connects to end of an electrical generator manufactured by General Electric Power & Water division, USA.

The unit houses various equipment such as the generator collector and turning gear assemblies which are used to start the system and to draw power off during operation.  The unit also contains various piping and instrumentation related to the generator monitoring, seal oil supply/drain systems, and hydrogen purging systems.  Additionally the unit has gas monitoring, ventilation, lighting, and fire detection/suppression systems installed. 

The B9G1 Collector CAB is not a standalone system and is not functional until it is interconnected with a General Electric and properly installed in a Gas Turbine Power Plant.     

Junction Boxes in the B9G1 Collector CAB Assembly clearly presents instructions for wiring interconnections and field wiring during final installation of equipment. Instructions for safety, putting into service; use; assembling and dismantling; maintenance, overhaul and repair; Installation; adjustment; is responsibility of General Electric Power & Water division, USA. 

 

NOTE: Although this equipment is covered under a Full Certificate supported by the ExTR and QAR listed, each unit is inspected and verified by the ExCB upon completion. This Certificate covers only the Model Number and Serial Number listed in the “Electrical Apparatus” section on page 1 of this Certificate.

 

 

 
SPECIFIC CONDITIONS OF USE: YES as shown below:
 

1) Hazardous Area Drawing 124E4881 defines the boundaries between various hazardous classified areas within the skid B9G1 CAB and the associated non-hazardous zones.  Is the responsibility of the installer to maintain the hazardous area envelop, as defined in the drawing 124E4881 in accordance with the area classification procedures of IEC 60079-10-1 

 

2) For maximum number of conductors for the housing size and permissible current rating of field wiring and interconnections of junction boxes tag numbers  jb5h, jb508, jb163, jb5a and jb166 refer to R. Stahl manufacturer instructions attached to IECEx PTB 09.0048 issue.

 