IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx SIR 12.0063 issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2012-05-24 Page 1 of 4


    
Applicant:
Druck Ltd
Fir Tree Lane
Groby
Leicester LE6 0FH
United Kingdom


 
Electrical Apparatus:Analogue Output Pressure Transducer Types SPT660-5271 and SPT660-5337
Optional accessory:


 
Type of Protection:Intrinsic Safety


 
Marking:

Ex ia IIB T4 Ga
(Ta = -20°C to +80°C)

 
Approved for issue on behalf of the IECEx
Certification Body:
C Ellaby

 
Position:Deputy Certification Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
SIRA Certification Service
Rake Lane
Eccleston
Chester
CH4 9JN
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 12.0063
 
Date of Issue:2012-05-24Issue No.: 0
 
Page 2 of 4
 
 Manufacturer:
Druck Ltd
Fir Tree Lane
Groby
Leicester LE6 0FH
United Kingdom


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2011
Edition: 6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-11 : 2011
Edition: 6.0
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-26 : 2006
Edition: 2
Explosive atmospheres - Part 26: Equipment with equipment protection level (EPL) Ga
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/SIR/ExTR12.0122/00


Quality Assessment Report:

GB/BAS/QAR06.0059/03


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 12.0063
 
Date of Issue:2012-05-24Issue No.: 0
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

The Analogue Output Pressure Sensors, Types SPT660-5271 (5000 psi and 10000 psi ranges) and SPT660-5337 (10000 psi ranges), are self contained pressure transducer assemblies that are designed to be located on a rig standpipe.  They comprise two printed circuit boards (PCBs) and a strain gauge module all located and encapsulated in a mainly stainless steel enclosure, with some alloy (inconel) parts, that affords a degree of ingress protection of at least IP54.  A multipin connector provides the connection facilities for the external circuits.  The differences between the SPT660-5271 and the SPT660-5337 sensors are in the threaded fittings, in addition, the SPT660-5337 is only produced as a 10000 psi sensor.

 
Refer to EQUIPMENT (continued) for Electrical Input parameters.
 
CONDITIONS OF CERTIFICATION: NO
 
 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 12.0063
 
Date of Issue:2012-05-24Issue No.: 0
 
Page 4 of 4
 
 
EQUIPMENT(continued):
 
Electrical Input parameters
Power supply, pin C wrt 0V, supply ground pin DStatic output, pin E, wrt to signal ground, pin B
Ui = 28 VUi = 28 V
Ii = 93 mAIi = 93 mA
Pi = 0.65 WPi = 0.65 W
Dynamic output, pin A, wrt to signal ground, pin BSignal ground, pin B, and power supply ground, pin D
Ui = 28 VUi = 2 V
Ii = 93 mAIi = 400 mA
Pi = 0.65 WPi = 0.2 W
The combined input parameters for the pressure transducers are as follows:
Ui = 28 V 
Ii = 679 mA 
Pi = 2.15 W 
Ci = 0.3322 µF 
Li = 0 
 
 
 







Copyright © IEC-IECEx 2013 , Geneva Switzerland. All rights reserved.