IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx KEM 07.0014X issue No.: 3
 
Status:
Current
 
Date of Issue:2015-02-10Page 1 of 4
 
 
Applicant:
Hummel AG
Lise-Meitner-Straße 2
79211 Denzlingen
Germany
Equipment:Cable glands, Series HSK-K-MZ-Ex, HSK-M-Ex, HSK-M-PVDF-Ex, HSK-M-EMV-Ex, HSK-M-PVDF-EMV-Ex, HSK-M-EMV-D-Ex, HSK-MZ-Ex, HSK-MZ-PVDF-Ex, HSK-MZ-EMV-Ex, HSK-MZ-PVDF-EMV-Ex, HSK-INOX-Ex, HSK-INOX-PVDF-Ex, HSK-INOX-EMV-Ex and HSK-INOX-PVDF-EMV-Ex
 
Optional accessory:
 
Type of Protection:e, ta

 Marking:

Ex e IIC Gb
Ex ta III C Da

 
 
Approved for issue on behalf of the IECEx
Certification Body:
T. Pijpker

 
Position:Certification Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

  Certificate issued by:
DEKRA Certification B.V.
Meander 1051
6825 MJ Arnhem
The Netherlands


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx KEM 07.0014X
 
Date of Issue:2015-02-10Issue No.: 3
 
Page 2 of 4
  
Manufacturer:
Hummel AG
Lise-Meitner-Straße 2
79211 Denzlingen
Germany


 
Additional Manufacturing location(s):
Hummel AG
Mozartstraße 3
79183 Waldkirch
Germany

 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2011
Edition: 6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-31 : 2013
Edition: 2
Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure "t"
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:

NL/DEK/ExTR11.0041/00NL/DEK/ExTR11.0041/01NL/KEM/ExTR06.0059/00NL/KEM/ExTR08.0026/00


Quality Assessment Report:

DE/BVS/QAR07.0001/06


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx KEM 07.0014X
 
Date of Issue:2015-02-10Issue No.: 3
 
Page 3 of 4
 
Schedule
 EQUIPMENT:
Equipment and systems covered by this certificate are as follows
 
 
Cable glands, Series HSK-K-MZ-Ex, HSK-M-Ex, HSK-M-PVDF-Ex, HSK-M-EMV-Ex, HSK-M-PVDF-EMV-Ex, HSK-M-EMV-D-Ex, HSK-MZ-Ex, HSK-MZ-PVDF-Ex, HSK-MZ-EMV-Ex, HSK-MZ-PVDF-EMV-Ex, HSK-INOX-Ex, HSK-INOX-PVDF-Ex, HSK-INOX-EMV-Ex and HSK-INOX-PVDF-EMV-Ex in type of protection increased safety "e" or equipment dust ignition protection by enclosure "t". 
Available thread sizes are M12 to M63, PG7 to PG48 and  3/8" to 1 1/2" NPT.

Operating temperature range:  -60 °C to +95 °C (standard versions HSK-M and HSK-INOX)
                                                 -20 °C to +130 °C (PVDF versions HSK-M and HSK-INOX)
                                                 -20 °C to +70 °C (HSK-K-MZ-Ex)

The cable glands provide a degree of protection of IP68 in accordance with IEC 60529.


 SPECIFIC CONDITIONS OF USE:   YES as shown below:
 
 
- The cable glands Series HSK-K-MZ-Ex are tested for low risk of mechanical danger (drop height 0.4 m with 1 kg mass) and shall be protected against higher impact energy levels.
 
- The cable glands Series HSK-M-...-Ex and HSK-INOX-...-Ex are tested with a reduced tensile force (25 %) in accordance with clause A.3.1 of IEC 60079-0 and may only be used for fixed installation of Group II apparatus. The user shall ensure adequate clamping of the cable.
 


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx KEM 07.0014X
 
Date of Issue:2015-02-10Issue No.: 3
 
Page 4 of 4
 
 DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 
 

- Assessment against the latest standard editions.
- Name changes of three types of Cable Glands. The details are listed in the Addendum of the applicable ExTR; NL/DEK/ExTR11.0041/01

 
 