Certificate No.:
IECEx BAS 04.0014 issue No.:0
 
Status:
Current
 
Date of Issue:2004-05-24 Page 1 of 4


    
Applicant:
Pepperl + Fuchs GB Limited
Oldham
Lancashire
OL1 4EL
United Kingdom


 
Equipment:Type KFD2-(S)CD2-Ex*.LK Transformer Isolated Driver
Optional accessory:


 
Type of Protection:Intrinsic Safety


 
Marking: IECEx BAS 04.0014
[Ex ia]IIC
[Ex ia]I
-20°C ≤ Ta ≤ +60°C
 
Approved for issue on behalf of the IECEx
Certification Body:
R S Sinclair

 
Position:Managing Director


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Baseefa
Rockhead Business Park
Staden Lane
Buxton, Derbyshire, SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 04.0014
 
Date of Issue:2004-05-24Issue No.: 0
 
Page 2 of 4
 
 Manufacturer:
Pepperl + Fuchs GmbH
Konigburger Allee 87
68307 Mannheim
Germany


 
 Additional Manufacturing location(s):
Pepperl + Fuchs PTE LTD
P + F Building
18 Ayer Rajah Crescent
SINGAPORE 139942
Singapore
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2000
Edition: 3.1
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-11 : 1999
Edition: 4
Electrical apparatus for explosive gas atmospheres - Part 11: Intrinsic safety 'i'
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
IECEx ATR:File Reference:
UK/BAS/03/1011   03/1011  
   
   


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 04.0014
 
Date of Issue:2004-05-24Issue No.: 0
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 
The Transformer Isolated Driver Type KFD2-(S)CD2-Ex*.LK is a single or two channel device designed to provide galvanic isolation between intrinsically safe apparatus located in a hazardous area and associated apparatus located in a non-hazardous area and limit the voltage and current into the hazardous area to intrinsically safe levels.

The apparatus comprises a number of electrical components, including transformers, fuses, resistors and zener diodes, all mounted on a single printed circuit board and housed within a plastic enclosure.

The use of '*' in the type description may be '1' or '2' for single or two channel respectively.

The use of 'S' in the type description specifies SMART versions; no 'S' signifying non-SMART versions.

The apparatus is designed to operate from a d.c. supply of up to 35V on terminals 7 to 9, terminals 10 to 12 (second channel), terminals 14 and 15 and on power rail connector terminals 1, 2 and 4. The segregation of the hazardous area circuits meets the requirements for 250V.

For electrical data see Additional information.
 
SPECIFIC CONDITIONS OF USE: NO
 
 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 04.0014
 
Date of Issue:2004-05-24Issue No.: 0
 
Page 4 of 4
 
 
Additional information:
 
Two Channel Transformer Isolated Driver Type KFD2-(S)CD2-Ex2.LK

Terminals 7 to 12, 14 and 15 and power rail terminals 1, 2 and 4

Um = 250V

Terminals 1 and 2 (Channel 1) and Terminals 4 and 5 (Channel 2)

Uo = 25.2V
Io = 93mA
Po = 585mW

Ci = 0
Li = 0

The capacitance and either the inductance or the inductance to resistance ratio (L/R) of the hazardous area load must not exceed the following values:

Group Capacitance, µF Inductance, mH OR L/R Ratio, µH/ohm
IIC 0.107 3.05 (4.2) 60
IIB 0.82 9.15 (17) 243
IIA 2.9 24.4 (33) 486
I 4.3 26 787

When the external circuit contains no lumped inductance i.e. the Li of any attached apparatus is zero, the cable inductance may be increased to the values within parentheses.

Single Channel Transformer Isolated Driver Type KFD2-(S)CD2-Ex1.LK

Terminals 7 to 9, 14 and 15 and power rail terminals 1, 2 and 4

Um = 250V

Terminals 1 and 2 (Channel 1)

Uo = 25.2V
Io = 93mA
Po = 585mW

Ci = 0
Li = 0

Load parameters are unchanged.

 
 