IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BVS 11.0061 issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2011-09-19 Page 1 of 4


    
Applicant:
Pepperl+Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
Electrical Apparatus:Wireless Adapter type WHA-ADP-F8B2-*-**-Z1***
Optional accessory:


 
Type of Protection:Intrinsic safety 'i', Protection by enclosure 't'


 
Marking: for WHA-ADP-F8B2-*-P*-Z1*** Ex ia IIC T4 Gb
-----------------------------------------------------
for WHA-ADP-F8B2-*-A*-Z1*** Ex ia IIC T4 Gb
Ex tb [ia] IIIC T70C Db
IP6x
 
Approved for issue on behalf of the IECEx
Certification Body:
H.-Ch. Simanski

 
Position:Head of Certification Body


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
DEKRA EXAM GmbH
Dinnendahlstrasse 9
44809 Bochum
Germany


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BVS 11.0061
 
Date of Issue:2011-09-19Issue No.: 0
 
Page 2 of 4
 
 Manufacturer:
Pepperl+Fuchs GmbH
Lilienthalstr. 200
68307 Mannheim
Germany


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2007-10
Edition: 5
Explosive atmospheres - Part 0:Equipment - General requirements
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-31 : 2008
Edition: 1
Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure 't'
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
DE/BVS/ExTR11.0096/00


Quality Assessment Report:

DE/PTB/QAR06.0007/02


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BVS 11.0061
 
Date of Issue:2011-09-19Issue No.: 0
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 
Description
 
 
The WirelessHART-Adapter Type WHA-ADP-F8B2-*-**-Z1*** is a battery powered interface module that connects HART and 4…20 mA devices to a WirelessHART network. The wireless Adapter transmits the information to a host application and operates with 2.4 GHz. As battery the battery type W-BAT-B2-Li is used.
 
Permissible ambient temperature range of the WirelessHart-Adapter: -40 °C up to +60 °C 
 
 
 
Type designation
 
See Annex
 
CONDITIONS OF CERTIFICATION: NO
 
 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BVS 11.0061
 
Date of Issue:2011-09-19Issue No.: 0
 
Page 4 of 4
 
 
EQUIPMENT(continued):
 

Electrical data
1. adapter active intrinsically safe (terminal 1-2)    
 voltageUo    26 VDC
 currentIo   98mA
 power Po631mW
 internal resistance Ri266 Ω
 effective internal capacitance Ci   20nF
 effective internal inductance Li120µH
 max external capacitance Co  80nF
 max external inductance Lo    3.6mH 
     
2.adapter passive (terminal 2-3)    
 voltage Ui  30VDC
 current Ii100mA
 powerPi     3W
 effective internal capacitanceCinegligible  
 effective internal inductance Li negligible 
     
3. adapter passive/active; only HART communication (terminal 4-6)   
 voltage Uo     6.7 VDC
 currentIo     1.7 mA
 powerPo     2.7mW
 voltage Ui   30VDC
 effective internal capacitance Ci negligible  
 effective internal inductance

Li

negligible 
 max external capacitanceCo   80 nF
 max external inductance Lo    3.6mH
     
4.HF-output antenna   
 transmissions frequency      2.4 GHz
 output power (nominal)   10mW
 output power (under 2 faults)     1.05 W
 under the regulation of the IEC 60079-0   
     
5.ambient temperature range -40 °C up to +60 °C
 
 
 







Copyright © IEC-IECEx 2016 , Geneva Switzerland. All rights reserved.