IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BAS 06.0025 issue No.: 1
 
Status:
Current
 
Date of Issue:2006-12-11Page 1 of 4
 
 
Applicant:
Pepperl + Fuchs GmbH
Königsberger Allee 87
68307 Mannheim
Germany
Equipment:Type KCD2-SR-Ex*.* Switch Amplifier
 
Optional accessory:
 
Type of Protection:Intrinsic Safety

 Marking:

IECEx BAS 06.0025
[Ex ia] IIC
[Ex ia] I
-20 °C ≤ Ta ≤ +60 °C

 
 
Approved for issue on behalf of the IECEx
Certification Body:
R S Sinclair

 
Position:Managing Director


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

  Certificate issued by:
SGS Baseefa Limited
Rockhead Business Park
Staden Lane
Buxton, Derbyshire, SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx BAS 06.0025
 
Date of Issue:2006-12-11Issue No.: 1
 
Page 2 of 4
  
Manufacturer:
Pepperl + Fuchs GmbH
Königsberger Allee 87
68307 Mannheim
Germany


 
Additional Manufacturing location(s):
Pepperl + Fuchs PTE Ltd
P + F Building
18 Ayer Rajah Crescent
Singapore 139942
Singapore

 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2000
Edition: 3.1
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-11 : 1999
Edition: 4
Electrical apparatus for explosive gas atmospheres - Part 11: Intrinsic safety 'i'
IEC 60079-26 : 2004
Edition: 1
Electrical apparatus for explosve gas atmospheres - Part 26: Construction, test and marking of Group II Zone 0 electrical apparatus
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:

GB/BAS/ExTR06.0025/00


Quality Assessment Report:

DE/PTB/QAR06.0008/00


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx BAS 06.0025
 
Date of Issue:2006-12-11Issue No.: 1
 
Page 3 of 4
 
Schedule
 EQUIPMENT:
Equipment and systems covered by this certificate are as follows
 
 

The Type KCD2-SR-Ex*.* Switch Amplifiers are designed to transfer digital signals from the hazardous area to unspecified apparatus located in the non-hazardous area. The voltage and current passed to the hazardous area are limited to intrinsically safe levels and have linear characteristics. Up to two hazardous area channels are fitted and are galvanically isolated from the non-hazardous area circuit using transformers.

The Type KCD2-SR-Ex*.* Switch Amplifier comprise a number of electronic components, including isolating transformers, fuses, zener diodes and resistors all mounted on a single printed circuit board and housed in a plastic enclosure with polarised plug-in terminals for hazardous and non-hazardous area connections. The non-hazardous area connections are via relay contacts with configuration switches allow the setting of the direction of operation and lead monitoring. LED indication is provided for power-on and channel status.

There are three models of the Type KCD2-SR-Ex*.* Switch Amplifier, the Type KCD2-SR-Ex2 Two Channel Switch Amplifier, the Type KCD2-SR-Ex1 Single Channel Switch Amplifier and the type KCD2-SR-Ex1.LB Single Channel Switch Amplifier. The Types KCD2-SR-Ex1 and KCD2-SR-Ex1.LB are depopulated versions of the KCD2-SR-Ex2 with only one hazardous area channel.   
   
See Annex for electrical parameters.



 SPECIFIC CONDITIONS OF USE:   NO
 
 
 


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx BAS 06.0025
 
Date of Issue:2006-12-11Issue No.: 1
 
Page 4 of 4
 
 DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 
 

IECEx Certificate Variation

Variation 1.1

To permit a minor change to the transformer design not affecting the original assessment.

ExTR: GB/BAS/ExTR06.0166/00

File Reference: 06/0971

 
 




Copyright © IEC-IECEx 2019 , Geneva Switzerland. All rights reserved.