IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx KIWA 15.0017X issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2015-10-16 Page 1 of 4


    
Applicant:
Pepperl + Fuchs GmbH
Lilienthalstraße 200
68307 Mannheim
Germany


 
Electrical Apparatus:SMART Transmitter Power Supply Model HiC2025 and SMART Current Driver Model HiC2031
Optional accessory:


 
Type of Protection:Ex nA


 
Marking: Ex nA IIC T4 Gc
 
Approved for issue on behalf of the IECEx
Certification Body:
Pieter van Breugel

 
Position:Certification Officer


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Kiwa Nederland B.V. (Unit Kiwa ExVision)
Wilmersdorf 50
7327 AC Apeldoorn
P.O. Box 137
7300 AC Apeldoorn
The Netherlands


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx KIWA 15.0017X
 
Date of Issue:2015-10-16Issue No.: 0
 
Page 2 of 4
 
 Manufacturer:
Pepperl + Fuchs GmbH
Lilienthalstraße 200
68307 Mannheim
Germany


 
 Additional Manufacturing location(s):
Pepperl + Fuchs PTE Ltd.
18 Ayer Rajah Crescent
Singapore 139942
Singapore
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2011
Edition: 6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-15 : 2010
Edition: 4
Explosive atmospheres - Part 15: Equipment protection by type of protection "n"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
NL/KIWA/ExTR15.0015/00


Quality Assessment Report:

DE/PTB/QAR06.0007/04DE/PTB/QAR06.0008/06


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx KIWA 15.0017X
 
Date of Issue:2015-10-16Issue No.: 0
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

SMART Transmitter Power Supply Model HiC2025 is for the supply of intrinsically safe transmitters located in an explosive atmosphere and can also be used with an active intrinsically safe current source. It transfers the analog input signal to the non-intrinsically safe side as an isolated current signal.
Bi-directional communication is supported for transmitters that use current modulation to transmit data and voltage modulation to receive data.

SMART Current Driver Model HiC2031 repeats a 4 - 20 mA input signal from a non-intrinsically safe source to drive intrinsically safe HART I/P converters, valve actuators, and displays located in an explosive atmosphere.

The modules mount into a HiC Termination Board.

Ambient temperature range -20 ºC to +60 ºC.

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 

The modules shall be installed in an enclosure or cabinet that at least is in compliance with the requirements of the standards listed and that provides a degree of protection of at least IP54.

Provision shall be made externally to provide transient protection, set at a level not exceeding a peak voltage of 119 V.

The modules may only be disconnected from or connected to the HiC Termination Board if the system is de-energized or if no explosive atmosphere is present.

The use of operating elements is only allowed if if the system is de-energized or if no explosive atmosphere is present.

 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx KIWA 15.0017X
 
Date of Issue:2015-10-16Issue No.: 0
 
Page 4 of 4
 
 
EQUIPMENT(continued):
 

Electrical data

Model HiC2025

Supply:
19 ... 30 V (via Termination Board),
rated current maximum 45 mA,
power maximum 1.1 W.

Output:
4 ... 20 mA or 1 ... 5 V on maximum 300 Ω (source mode) or
4 ... 20 mA, 15 … 26 Vdc (sink mode).

Model HiC2031

Supply:
19 ... 30 V (via Termination Board),
rated current maximum 30 mA,
power maximum 700 mW.

Input:
4 ... 20 mA (max. 30 mA),
maximum 27 V.

For data of the intrinsically safe input, respectively output circuits, refer to Certificate of Conformity
IECEx CES 06.0002.

 
 
 