Certificate No.:
IECEx SIR 08.0126U issue No.: 5
 
Status:
Current
 
Date of Issue:2018-03-06Page 1 of 4
 
 
Applicant:
International Metal Engineering Pte Ltd
Blk 13
Toa Payoh Lorong 8
# 06-05 Braddell Tech Park
319261
Singapore
Equipment:7100, 8100, 8100Vx 8100Px and 8100K Series of Instrument Enclosures and Junction Boxes
 
Optional accessory:
 
Type of Protection:Flameproof and Dust

 Marking:

Ex db IIC Gb
Ex tb Db IIIC
Ta = -40°C to +85°C

 
 
Approved for issue on behalf of the IECEx
Certification Body:
C Ellaby

 
Position:Deputy Certification Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

  Certificate issued by:
SIRA Certification Service
CSA Group
Unit 6, Hawarden Industrial Park
Hawarden, Deeside, CH5 3US
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx SIR 08.0126U
 
Date of Issue:2018-03-06Issue No.: 5
 
Page 2 of 4
  
Manufacturer:
International Metal Engineering Pte Ltd
Blk 13
Toa Payoh Lorong 8
# 06-05 Braddell Tech Park
319261
Singapore


 
Additional Manufacturing location(s):

 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2011
Edition: 6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-1 : 2014-06
Edition: 7.0
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 60079-31 : 2013
Edition: 2
Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure "t"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:

GB/SIR/ExTR09.0100/00GB/SIR/ExTR09.0138/00GB/SIR/ExTR13.0033/00GB/SIR/ExTR14.0034/00GB/SIR/ExTR18.0014/00


Quality Assessment Report:

GB/SIR/QAR07.0040/00


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx SIR 08.0126U
 
Date of Issue:2018-03-06Issue No.: 5
 
Page 3 of 4
 
Schedule
 EQUIPMENT:
Equipment and systems covered by this certificate are as follows
 
 

8100Px

The 8100Px instrument enclosures and junction boxes are cylindrical single compartment enclosures comprising a base and cover with a maximum internal volume of 700 cm³. The enclosures are manufactured from cast aluminium with an epoxy paint finish. The enclosures cover may be solid aluminium or contain a circular tempered glass window. Each enclosure may have up to three conduit openings with entry sizes selected from ½” NPT, ¾” NPT, ½” BSP or M20x1.5.

Refer to the Annexe for additional Information, Design options and the Schedule of Limitations.



 SPECIFIC CONDITIONS OF USE:   NO
 
 
 


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx SIR 08.0126U
 
Date of Issue:2018-03-06Issue No.: 5
 
Page 4 of 4
 
 DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 
 

This issue recognises, Issue 5, the following changes; refer to the certificate annex to view a comprehensive history:

  1. Following appropriate assessment to demonstrate compliance with the latest technical knowledge, IEC 60079-1:2007 Ed.6 and IEC 60079-31:2008 Ed.1 were replaced by IEC 60079-1:2014 Ed.7 and IEC 60079-31:2013 Ed.2, the markings were updated accordingly to recognise the new standards, and a Schedule of Limitations was added.
  2. Other external thread types (other than metric or NPT) are not permitted as an option for cable glands in field wiring installations in IEC 60079-1:2014 Annex C.2.2, therefore a specific condition of use is added to this certificate.
 
 