IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx FMG 11.0023X issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2012-03-01 Page 1 of 3


    
Applicant:
JB Systems Inc.
4944 113th Ave. N.
Clearwater, FL 33760
United States of America


 
Electrical Apparatus:IRIS U2 (Uniscan2) Flame Monitoring System
Optional accessory:


 
Type of Protection:Flameproof; Non-sparking; Dust Ignition Protection by Enclosure


 
Marking:

Ex d IIC T6 Gb Ta = -40C to +70C
Ex nA nC IIC T5 Gc Ta = -40C to +70C
Ex tb IIIC T85C Db Ta = -40C to +70C  IP66

 
Approved for issue on behalf of the IECEx
Certification Body:
James E. Marquedant

 
Position:Group Manager - Electrical


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
FM Approvals LLC
1151 Boston-Providence Turnpike
Norwood, MA 02062
United States of America


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx FMG 11.0023X
 
Date of Issue:2012-03-01Issue No.: 0
 
Page 2 of 3
 
 Manufacturer:
JB Systems Inc.
4944 113th Ave. N.
Clearwater, Fl 33760
United States of America


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2007-10
Edition: 5
Explosive atmospheres - Part 0:Equipment - General requirements
IEC 60079-1 : 2007-04
Edition: 6
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 60079-15 : 2005-03
Edition: 3
Electrical apparatus for explosive gas atmospheres Part 15: Construction, test and Marking of Type of Protection "n" electrical apparatus
IEC 60079-31 : 2008
Edition: 1
Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure 't'
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
US/FMG/ExTR11.0025/00


Quality Assessment Report:

US/FMG/QAR10.0001/00


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx FMG 11.0023X
 
Date of Issue:2012-03-01Issue No.: 0
 
Page 3 of 3
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

IRIS U2 (Uniscan 2) Flame Monitoring System:

Models, 1010 / 1010-PF; 1012/ 1012-PF; 1016 / 1016-PF; 1018 / 1018-PF

 

 

 

 

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 

1.      Consult the manufacturer if dimensional information on the flameproof joints is necessary.

2.      The aluminum surface of the IRIS U2 Flame Monitoring Sys may store electrostatic charge and become a source of ignition in applications with a low relative humidity <30% relative humidity where the aluminum surface is relatively free of surface contamination such as dirt, dust or oil.  Cleaning of the painted surface should only be done with a damp cloth.

3.      The apparatus has flying lead conductors that exit the enclosure.  A suitably certified Ex d or Ex e terminal box is required to be connected to apparatus enclosure for completing to external supply circuits. 

 

 







Copyright © IEC-IECEx 2013 , Geneva Switzerland. All rights reserved.