Certificate history:
Ex e IIC Gb
Ex tb IIIC Db
IP66
This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.
This Unit verification certificate is issued as verification that the Apparatus identified on page 1, was assessed and tested and found to comply with the IEC Standard list below. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.
STANDARDS: The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:
As this is a Unit Verification Certificate, no QAR is applicable as this certificate is specific to the items listed by serial number or other unique identification.
Command actuators series M-0603, M-0604 and M-0605 for Ex e housing are used as external devices that passing through enclosure wall, which must have a hole of diameter 32mm and thickness between 1mm and 10mm. With these conditions the operators have a protection degree IP66.
The actuators are essentially made by an axial shaft which is mounted in a body. This assembly is then mounted and mechanically locked by ring nut in an adequate centre (diameter 32mm with tolerances +0.00mm, +0.10mm).
Push button and emergency maintained push button have axial motion. Maintained push button have an axial motion when push-it, then lock. For unlock must rotate clockwise and it returns automatically in original position. Selector have a rotary motion so to provide closing or opening of various electrical or mechanical devices mounted internally on enclosures.
Model Identification:
M-0603 : Push button actuator;
M-0604 : Selector actuator;
M-0605 : Maintained push button actuator.
Technical characteristics:
- Diameter of enclosure through-hole: 32 mm
- Service Temperature Range: - 40 ÷ + 90 °C
- Degree of protection: IP 66 (IEC 60529)
Schedule of limitations for components:
- Rated service temperature range: from -40°C to +90°C.
- The command actuators must be assembled on the cover or walls of metallic and/or plasticenclosures, IECEx certified, for group IIC, with increased safety type of protection (Ex“e”) and group III (dust) with suitable degree of protection IP.
- Command actuators shall be mounted on the enclosure with thickness from 1mm to 10mm and a hole of diameter 32mm with tolerances +0 mm / +0,10 mm.
- When the component are installed on to the electrical apparatus, care must be taken that the temperatures at the mounting place are within the service temperature range.
- The safety instruction provided by Manufacturer shall be strictly respected.