Certificate No.:
IECEx BAS 06.0013X issue No.:6
 
Status:
Current
 
Date of Issue:2012-03-14 Page 1 of 4


    
Applicant:
Hawke International
A Division of Hubbell Ltd.
A member of the Hubbell Group of Companies
Oxford Street West, Ashton-under-Lyne
Lancashire, OL7 0NA
United Kingdom


 
Electrical Apparatus:A Range of Compression Type Cable Glands,
Optional accessory:


 
Type of Protection:Ex d, Ex e, Ex tb


 
Marking: Ex d IIC Ex e IIC Gb
Ex tb IIIC Db IP66
(- 60°C ≤ ta ≤ + 100°C) see schedule
 
Approved for issue on behalf of the IECEx
Certification Body:
R S Sinclair

 
Position:General Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Baseefa
Rockhead Business Park
Staden Lane
Buxton
Derbyshire
SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 06.0013X
 
Date of Issue:2012-03-14Issue No.: 6
 
Page 2 of 4
 
 Manufacturer:
Hawke International
A Division of Hubbell Ltd.
A member of the Hubbell Group of Companies
Oxford Street West
Ashton-under-Lyne
Lancashire
OL7 0NA
United Kingdom


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2007-10
Edition: 5
Explosive atmospheres - Part 0:Equipment - General requirements
IEC 60079-1 : 2007-04
Edition: 6
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 60079-31 : 2008
Edition: 1
Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure 't'
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/BAS/ExTR06.0011/00GB/BAS/ExTR08.0173/00GB/BAS/ExTR09.0165/00GB/BAS/ExTR10.0287/00GB/BAS/ExTR11.0274/00


Quality Assessment Report:

GB/BAS/QAR06.0061/02


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 06.0013X
 
Date of Issue:2012-03-14Issue No.: 6
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

A range of compression type cable glands manufactured in brass, stainless steel or aluminium. The glands may be supplied with metric or specified non-metric equivalent thread forms. These glands are intended for use with effectively filled circular cables. The cable type and/or cable protection/retention method is specific to each gland type designation – see annex for detail.

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 

1.  These glands are suitable for use within an operating temperature range of -60oC to +80oC, or +100oC for the gland types not using the iris type outer seal assembly.

2.  When the gland is used for increased safety or dust protection, the entry thread shall be suitably sealed in accordance with IEC 60079-14 to maintain the ingress protection rating of the associated enclosure

3.  Glands for use with conduit, unarmoured or braided cables are only suitable for fixed installations, the cable for which must be effectively clamped to prevent pulling and twisting (does not apply to variation 6.3).

 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 06.0013X
 
Date of Issue:2012-03-14Issue No.: 6
 
Page 4 of 4
 
 
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 

Variation 6.1

To allow the replacement of the 7o armour clamping components with 5o armour clamping components on gland sizes Os, O and A.

Variation 6.2

The introduction of a range of non reversible dedicated armour clamping rings, in this form the RAC stamping is replaced by DED followed by W, X, Y or Z to indicate the type of armour that may be fitted.

Variation 6.3

To allow the introduction of a rear clamping mechanism to the 501/421 gland size B, in this form the gland is designated 501/421R.

For variation 6.3 Condition of Cetification No. 3 does not apply.

 ExTR:  GB/BAS/ExTR011.0274/00 held with this certificateFile Reference 11/0741 and 11/0943
  
 
 