IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BAS 10.0039X issue No.:3
 
Status:
Current
 
Date of Issue:2012-03-12 Page 1 of 4


    
Applicant:
Dong A Bestech Company Limited
13-16, Samjeong-Dong
Ojeong-Ku
Bucheon-City
Kyung Gi-Do
Korea, Republic of


 
Electrical Apparatus:DNLEX-A XXX Range of Cable Glands
Optional accessory:


 
Type of Protection:Flameproof, Increased Safety, Dust


 
Marking: Ex d IIC
Ex e II
Ex tD A21 IP66 -60°C ≤ ta ≤ +100°C
 
Approved for issue on behalf of the IECEx
Certification Body:
R S Sinclair

 
Position:General Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Baseefa
Rockhead Business Park
Staden Lane
Buxton
Derbyshire
SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 10.0039X
 
Date of Issue:2012-03-12Issue No.: 3
 
Page 2 of 4
 
 Manufacturer:
Dong A Bestech Company Limited
13-16, Samjeong-Dong
Ojeong-Ku
Bucheon-City
Kyung Gi-Do
Korea, Republic of


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-1 : 2003
Edition: 5
Electrical apparatus for explosive gas atmospheres - Part 1: Flameproof enclosure 'd'
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
IEC 61241-0 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
IEC 61241-1 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 1: Protection by enclosures "tD"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/BAS/ExTR10.0066/00GB/BAS/ExTR10.0294/00GB/BAS/ExTR11.0110/00GB/BAS/ExTR12.0050/00


Quality Assessment Report:

GB/BAS/QAR07.0030/03


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 10.0039X
 
Date of Issue:2012-03-12Issue No.: 3
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 
The DLNEX-A XXX Cable Glands are intended for use with an effectively filled and circular, single wire armoured, steel basket weave armoured or braided (screened) lead sheathed cable and comprises the following components, the metal components of which may be nickel plated to suit application:-

a.             An entry component, in the size range (M20 to M100)
b.             A displacement sealing ring
c.             A combined compression spigot, armour clamping cone and electrical connection clip
d.            An armour clamping ring for steel wire armour cable
e              An armour clamping ring for steel basket weave armour or braided(screened) cable 
f.              A middle nut
g.            An outer displacement seal
h.            A back nut

The glands may be manufactured in brass or stainless steel (except for the seals) and may be supplied with specified alternative entry thread forms NPT to ANSI/ASME B1.20.1. 

The XXX is used to define the size of cable gland e.g. 20a, 25 etc.

 

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 
1. These glands are suitable for use within an operating temperature range of -60°C to +100°C.

2. When the gland is used for increased safety or dust protection, the entry thread shall be suitably sealed, in accordance with IEC 60079-14, to maintain the ingress protection rating of the associated enclosure.

3. Glands for use with braided (screened) cables or armoured cables having an armour diameter less than 0.2mm are only suitable for fixed installations, the cable for which must be effectively clamped to prevent pulling and twisting.

4. The electrical connection between the lead sheathing and the gland shall not be critical to the function/safety of the attached equipment (i.e. not the sole earth bonding connection).

 

 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 10.0039X
 
Date of Issue:2012-03-12Issue No.: 3
 
Page 4 of 4
 
 
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 

Variation 3.1

To allow minor dimensional changes in length of the (W) Clamping rings

  
 ExTR:  GB/BAS/ExTR 12.0050/00File Reference:   12/0133
 
 
 








Copyright © IEC-IECEx 2013 , Geneva Switzerland. All rights reserved.