Certificate history:
This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.
This Unit verification certificate is issued as verification that the Apparatus identified on page 1, was assessed and tested and found to comply with the IEC Standard list below. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.
STANDARDS: The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:
As this is a Unit Verification Certificate, no QAR is applicable as this certificate is specific to the items listed by serial number or other unique identification.
The circuit breaker, type 8562/5.-….-… is an electric equipment of type of protection Flameproof enclosure “d”, which is designed to accommodate protective components. The circuit breaker is manufactured in four sizes. Connection is by means of the integrated terminals.
Nomenclature
Technical data
Notes for installation and operation
The circuit breaker shall be fitted in an enclosure that meets the requirements of an approved type of protection in accordance with IEC 60079-0, section 1.
When installing the circuit breaker in an enclosure designed to type of protection Increased Safety “e” as specified in IEC 60079-7, the clearance and creepage distances shown in section 4.4, section 4.5, and table 1 shall be duly considered.