Certificate No.:
IECEx SIR 06.0074 issue No.:7
 
Status:
Current
 
Date of Issue:2013-07-15 Page 1 of 4


    
Applicant:
Pepperl+Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
Equipment:Terminal Boxes
Optional accessory:


 
Type of Protection:Intrinsically Safe, Increased safety and Dust


 
Marking: For Zone 0
Ex ia IIC T* Ga (Ta – **°C to + **°C) or
For Zone 1
Ex e II T* Gb (Ta – **°C to + **°C) or
Ex tb IIIC Db IP6X T**°C T* (Ta – **°C to + **°C)
The temperature classifications and ambient temperature range is as follows:-
T6, T80°C (Ta – 50°C to + 40°C) or
T5, T95°C (Ta – 50°C to + 55°C) or
T4, T130°C (Ta – 50°C to + 85°C) or
T3, T160°C (Ta – 50°C to +120°C).
 
Approved for issue on behalf of the IECEx
Certification Body:
A C Smith

 
Position:Certification Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
SIRA Certification Service
Rake Lane
Eccleston
Chester
CH4 9JN
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 06.0074
 
Date of Issue:2013-07-15Issue No.: 7
 
Page 2 of 4
 
 Manufacturer:
Pepperl+Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
 Additional Manufacturing location(s):

Refer to the annexe for additional manufacturing locations
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-0 : 2007-10
Edition: 5
Explosive atmospheres - Part 0:Equipment - General requirements
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-31 : 2008
Edition: 1
Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure 't'
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/SIR/ExTR07.0068/00GB/SIR/ExTR09.0149/00GB/SIR/ExTR10.0130/00GB/SIR/ExTR10.0193/00GB/SIR/ExTR10.0194/00GB/SIR/ExTR11.0307/00GB/SIR/ExTR12.0056/00GB/SIR/ExTR12.0106/00GB/SIR/ExTR12.0266/00GB/SIR/ExTR13.0206/00


Quality Assessment Report:

AU/TSA/QAR06.0004/05DE/PTB/QAR06.0008/02DE/PTB/QAR06.0008/03DE/PTB/QAR06.0008/04DE/PTB/QAR06.0015/01DE/PTB/QAR06.0015/02DE/PTB/QAR06.0015/03DE/PTB/QAR10.0008/00DE/PTB/QAR10.0008/01GB/SIR/QAR07.0004/00US/UL/QAR07.0005/03US/UL/QAR07.0005/04US/UL/QAR07.0005/06


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 06.0074
 
Date of Issue:2013-07-15Issue No.: 7
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 
The AL/SL/RX/FXL and XL Ranges of terminal enclosures manufactured from stainless steel, mild steel, or aluminium are of folded and welded construction to IECEx SIR06.0073U, and fitted with specified terminals.
For full description see Annexe.
 
Conditions of manufacture
The Manufacturer shall comply with the following:
1. The enclosures manufactured from aluminium shall not be used within zone 0.
2.The type XL*11/FXL*11, XL*11/FXL*11D or XL*11/FXL*11S enclosures shall not be used within dust applications.
3.Intrinsically safe and non-intrinsically safe circuits which are fitted within the same enclosure shall be separated as required by IEC 60079-14.
 
CONDITIONS OF CERTIFICATION: NO
 
 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 06.0074
 
Date of Issue:2013-07-15Issue No.: 7
 
Page 4 of 4
 
 
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 

Issue 1 – this Issue introduced the following change:

1The recognition of the RX Range of Terminal Boxes, these are similar to the XL Range, but are only made from stainless steel and are only fitted with terminals; the Description has been modified to include these devices
Issue 2 – this Issue introduced the following changes:
1Following appropriate re-assessment to demonstrate compliance with the requirements of IEC 60079-0:2007 and IEC 60079-31:2008 the standards listed on page 2 were updated.
2The company name and address change was changed and alternative manufacturing sites were recognised.
3The use of alternative label materials was approved.
4The addition of a Datamatrix code on the label was endorsed.
Issue 3 – this Issue introduced the following changes:
1Actuators, indicator lamps, potentiometers and switch modules manufactured by Bartec GmbH certified under IECEx PTB 08.0037U, IECEx PTB 10.0014U, IECEx PTB 10.0017U and IECEx PTB 07.0046U were approved to be fitted within the enclosures
2Recognition of reduced assigned power ratings applied for when the switch modules manufactured by Bartec GmbH certified under IECEx PTB 07.0046U are fitted. The reduced maximum power ratings for the enclosures are listed in the Annexe.
Issue 4 – this Issue introduced the following change:
1The introduction of a new manufacturing location in Twinsburg Ohio.
Issue 5 – this Issue introduced the following change:
1The introduction of a double bit type lock as an alternative means of fixing for the FXL type enclosure was approved.
Issue 6 – this Issue introduced the following change:
1The Pepperl+Fuchs Manufacturing UK Limited site at Cornwallis Road was changed to The Woods Bank Estate, Woden Road West, Wednesbury, West Midlands WS10 7SU
Issue 7 – this Issue introduced the following change:
1.The introduction of the following alternative manufacturing locations was approved.
 Pepperl+Fuchs Inc., 4333 West Sam Houston Parkway, North Suite 150, Houston, Texas 77043, USA and Pepperl+Fuchs (Australia) Pty Ltd, 131-149 Link Drive, Campbellfield, Victoria, 3061, Australia
 
 








Copyright © IEC-IECEx 2016 , Geneva Switzerland. All rights reserved.