IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx UL 16.0051X issue No.: 0
 
Status:
Current
 
Date of Issue:2016-07-26Page 1 of 3
 
 
Applicant:
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany
Equipment:Power Feed Modules and Redundant Power Feed Modules, Models KFD2-EB2, KFD2-EB2.SP, KFD2-EB2.R4A.B, and KFD2-E2-R4A.B.SP
 
Optional accessory:
 
Type of Protection:Non-sparking "nA", Sealed "nC"

 Marking:

Ex nA nC IIC T4 Gc

 

 

-20°C to 60°C

 
 
Approved for issue on behalf of the IECEx
Certification Body:
Katy A. Holdredge

 
Position:Senior Staff Engineer


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

  Certificate issued by:
UL LLC
333 Pfingsten Road
Northbrook IL 60062-2096
United States of America


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx UL 16.0051X
 
Date of Issue:2016-07-26Issue No.: 0
 
Page 2 of 3
  
Manufacturer:
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
Additional Manufacturing location(s):
Pepperl+Fuchs Asia Pte. Ltd.
18 Ayer Rajah Crescent
Singapore 139942
Singapore
PT. Pepperl+Fuchs Bintan
JI. Asoka SD 56
Bintan Industrial Estate
Lobam, Bintan Island
Indonesia

 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2011
Edition: 6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-15 : 2010
Edition: 4
Explosive atmospheres - Part 15: Equipment protection by type of protection "n"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:

US/UL/ExTR16.0055/00


Quality Assessment Report:

DE/PTB/QAR06.0007/04DE/PTB/QAR06.0008/07


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx UL 16.0051X
 
Date of Issue:2016-07-26Issue No.: 0
 
Page 3 of 3
 
Schedule
 EQUIPMENT:
Equipment and systems covered by this certificate are as follows
 
 

Electrical Ratings: 20 – 30 Vdc

Contact Load: 30 V AC, 2A / 40 V DC, 2A 

 

Power Feed modules Models KFD2-EB2, and KFD2-EB2.SP.

 

Redundant Power Feed modules Models KFD2-EB2.R4A.B, and KFD2-E2-R4A.B.SP.

 

Power Rail UPR-03 and UPR-05.

       

KFD2-EB2

R4A

B

SP

I

II

III

IV

 

I – Model Series Designation

 

II – Redundant System

 

                R4A – Redundant System

 

III – Bus System

               

                B – Bus System

 

IV – Spring Terminals

               

                SP – Spring Terminals

 



 SPECIFIC CONDITIONS OF USE:   YES as shown below:
 
 

The device must be installed and operated only in surrounding enclosures that comply with the requirements for surrounding enclosures according to IEC 60079-0, are rated with the degree of protection IP54 according to IEC 60529. Opening of the surrounding enclosure must not be possible without the use of a tool.

 

 

The device must be installed and operated only in an environment that ensures a pollution degree 2 (or better) according to IEC 60664-1.

 

 




Copyright © IEC-IECEx 2019 , Geneva Switzerland. All rights reserved.