IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BAS 11.0080X issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2011-07-25 Page 1 of 3


    
Applicant:
STI srl
Via G.Pascoli 10a-b
24020 Gorle (BG)
Italy


 
Electrical Apparatus:The Field Barrier Type ID
Optional accessory:


 
Type of Protection:Flameproof and Intrinsic Safety


 
Marking: Ex d [ia Ga] IIC T5 / T6 Gb (-40°C ≤ Ta ≤ 80°C / 60°C)
 
Approved for issue on behalf of the IECEx
Certification Body:
R S Sinclair

 
Position:Managing Director


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Baseefa
Rockhead Business Park
Staden Lane
Buxton
Derbyshire
SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 11.0080X
 
Date of Issue:2011-07-25Issue No.: 0
 
Page 2 of 3
 
 Manufacturer:
STI srl
Via G.Pascoli 10a-b
24020 Gorle (BG)
Italy


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-0 : 2007-10
Edition: 5
Explosive atmospheres - Part 0:Equipment - General requirements
IEC 60079-1 : 2007-04
Edition: 6
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/BAS/ExTR11.0143/00GB/BAS/ExTR11.0146/00


Quality Assessment Report:

DE/TUN/QAR10.0007/01


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 11.0080X
 
Date of Issue:2011-07-25Issue No.: 0
 
Page 3 of 3
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

The Field Barrier Type ID comprises two identical sections which may be used for two separate intrinsically safe circuits. Each section is intended to provide two connections for a supply and a diode return path. Although the shunt zener diode barrier channels rely on a Safe Area external earth connection, this is not usually available for the hazardous area apparatus. 

The circuit components are mounted on a printed circuit board and this is encapsulated within an Ex d enclosure. The Safe Area (Non intrinsically safe) connections to the barrier enter the enclosure via an Ex d cable gland and are terminated at terminal blocks which emerge from the encapsulation in the terminal chamber. Two internal terminals are provided for the Safe Area Earth connection in addition to an external earth connection. The Hazardous Area (intrinsically safe) output wires emerge from the base of the metallic Ex d enclosure, since the barrier assembly is intended to be mounted directly on the outer wall of other equipment. The barrier enclosure provides a degree protection of at least IP20 to the encapsulated circuit and the Hazardous Area intrinsically safe output wires are intended to be terminated at terminals within the external equipment.

For Output Parameters See Annex.

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 
1. The Field Barrier Type ID external earth terminal and/or safe area terminals J1/2 & J2/2 must be provided with a high integrity insulated earth connection equivalent to a 4mm² copper conductor, which has a resistance of less than 1 ohm to the supply star point and which must not rely on any plug and socket connections.

2. The metallic enclosure is directly connected to earth and therefore the electrical circuits are not capable of withstanding the 500V isolation to earth or frame requirement of EN60079-11. This must be taken into account in any installation.

3. The output wires Red, Black, Brown and Yellow must be terminated within an enclosure which provides a degree of protection of at least IP20. The segregation between the two identical sections must be maintained as two separate intrinsically safe circuits unless the combination of the two sections has been considered.

 

 