IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BAS 11.0087U issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2011-09-15 Page 1 of 4


    
Applicant:
Musasino Company Limited
1-2-15 Minami-yukigaya,
Ohta-Ku,
Tokyo,
145-0066,
Japan


 
Electrical Apparatus:Presure Guage TPC-A
Optional accessory:


 
Type of Protection:Intrinsic Safety


 
Marking: Ex ia IIC Ga
 
Approved for issue on behalf of the IECEx
Certification Body:

 
Position:


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Baseefa
Rockhead Business Park
Staden Lane
Buxton
Derbyshire
SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 11.0087U
 
Date of Issue:2011-09-15Issue No.: 0
 
Page 2 of 4
 
 Manufacturer:
Musasino Company Limited
1-2-15 Minami-yukigaya,
Ohta-Ku,
Tokyo,
145-0066,
Japan


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-0 : 2007-10
Edition: 5
Explosive atmospheres - Part 0:Equipment - General requirements
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/BAS/ExTR11.0155/00


Quality Assessment Report:

GB/BAS/QAR09.0010/01


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 11.0087U
 
Date of Issue:2011-09-15Issue No.: 0
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 
The Pressure Gauge TPC-A is designed to measure the pressure of liquid in a tank and relay that information via a serial data link. The Pressure Gauge TPC-A is intended to be used with other certified equipment and incorporated into their certificates. It is mounted in a stainless steel enclosure which is then encapsulated with silicon resin. A short integral cable emerges from one end; it has a standard pressure thread fitting at the other end for connection to the process medium. The enclosure measures approximately 40mm diameter by 100mm long.

Input Parameters


Ui

=10.4VCi=0.107921μF
Ii=302mALi=0
Pi=1.16W   

(See Page 4 for Schedule of Limitations)
 
CONDITIONS OF CERTIFICATION: NO
 
 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 11.0087U
 
Date of Issue:2011-09-15Issue No.: 0
 
Page 4 of 4
 
 
EQUIPMENT(continued):
 
Schedule of Limitations

1              The component is suitable for use in apparatus having a Temperature Class of T5 in a 70ºC ambient.

2              If required for alternative ambient temperatures and Temperature Class, the component could be used up to 140°C and a maximum temperature rise above ambient of 30°C should be taken into account.
 
 
 







Copyright © IEC-IECEx 2013 , Geneva Switzerland. All rights reserved.