Certificate No.:
IECEx BAS 11.0118X issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2011-10-26 Page 1 of 3


    
Applicant:
Toshiba Mitsubishi - Electric Industrial Systems Corporation
Nagasaki Factory
6-14 Maruo-Machi
Nagasaki City
852-8004
Japan


 
Electrical Apparatus:A Type ICF-CHKRWXD11, 400H Frame, 4 Pole, Induction Motor rated at 450kW, 6600V, 60Hz.
Optional accessory:


 
Type of Protection:Flameproof


 
Marking: Ex d IIB T4 Gb
 
Approved for issue on behalf of the IECEx
Certification Body:
R S Sinclair

 
Position:Managing Director


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Baseefa
Rockhead Business Park
Staden Lane
Buxton
Derbyshire
SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 11.0118X
 
Date of Issue:2011-10-26Issue No.: 0
 
Page 2 of 3
 
 Manufacturer:
Toshiba Mitsubishi - Electric Industrial Systems Corporation
Nagasaki Factory
6-14 Maruo-Machi
Nagasaki City
852-8004
Japan


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2011
Edition: 6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-1 : 2007-04
Edition: 6
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/BAS/ExTR11.0234/00


Quality Assessment Report:

GB/BAS/QAR06.0037/02


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 11.0118X
 
Date of Issue:2011-10-26Issue No.: 0
 
Page 3 of 3
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

A Type ICF-CHKRWXD11, 400H Frame, 4 Pole, Induction Motor rated at 450kW, 6600V, 60Hz. 

The motor has a cooling fan attached at the non-drive end protected by a steel cowl, and is fitted with three separate terminal boxes of differing sizes to accommodate the electrical connections to the stator windings, an internal space heater and a series of RTDs to monitor and detect excessive stator winding temperatures.

Thermal monitoring of the shaft bearings at each end of the machine is provided by the fitment of separately certified RTD assemblies to IECEx BAS 08.0094X.

Cable entry holes are provided as specified on the certified drawings for the accommodation of flameproof cable entry devices, with or without the interposition of a flameproof thread adapter. Unused entries are to be fitted with suitable certified flameproof stopping plugs. The cable entry devices, thread adapters and stopping plugs shall be suitable for the equipment, the cable and the conditions of use and shall be separately certified as Equipment (not a Component).

The motor is rated for S1 duty (continuous) when connected to a 3 phase, sinusoidal, 60Hz supply having form and symmetry not worse than that defined in IEC 60034-1.

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 
1. Several of the flamepath gaps are specified tighter than the maximum shown in the standard. The manufacturer is to be consulted for particular gap specifications prior to any maintenance/repair work being undertaken.
 