IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx INE 09.0025X issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2010-08-27 Page 1 of 4


    
Applicant:
Pepperl+Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
Electrical Apparatus:Field transmitter type WHA-UT-F7B1-0-PP-Z1-Ex2
Optional accessory:


 
Type of Protection:ia


 
Marking: Pepperl+Fuchs GmbH
WHA-UT-F7B1-0-PP-Z1-Ex2
(Serial Number)
Ex ia IIC T4
IECEx INE 09.0025X
Tamb : -20C, +60C
WARNINGS:
Potential electrostatics charging hazard. See instructions.
Use only cell W-BAT-B1-Li provided by P+F.
 
Approved for issue on behalf of the IECEx
Certification Body:
Thierry HOUEIX

 
Position:Ex Certification Officer


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
INERIS
Institut National de l'Environnement Industriel
et des Risques
BP n2
Parc Technologique ALATA
F-60550 Verneuil-En-Halatte
France


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx INE 09.0025X
 
Date of Issue:2010-08-27Issue No.: 0
 
Page 2 of 4
 
 Manufacturer:
Pepperl+Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
 Additional Manufacturing location(s):
Pepperl + Fuchs
(Manufacturing) PTE LTD
18 ayer Rajah Crescent
Singapore 139942
Singapore
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-26 : 2004
Edition: 1
Electrical apparatus for explosve gas atmospheres - Part 26: Construction, test and marking of Group II Zone 0 electrical apparatus
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
FR/INE/ExTR09.0028/00


Quality Assessment Report:

DE/PTB/QAR06.0007/02DE/PTB/QAR06.0008/02


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx INE 09.0025X
 
Date of Issue:2010-08-27Issue No.: 0
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

The field transmitter WHA-UT-F7B1-0-PP-Z1-Ex2 is an I.S. instrument that takes temperature measurement with a thermocouple or an RTD and sends the results wirelessly to a gateway. The device can read up to two sensors simultaneously. The sensor input ports are suitable for connection in Zone 0. The sensors are not part of the present certification; only input and output parameters of the connections are detailed. An additional port is provided for temporary communication with HART compliant IS hand held communicator when commissioning or/and checking the status of the device.

The device is powered with a single primary cell identified and tested according to IEC 60079-11. The cell is provided by Pepperl+Fuchs, product name W-BAT-B1-Li, and can be replaced also when device is in the hazardous area. The device contains an RF module and a PCB antenna for wireless communications.

A foil keypad is placed on the front side of the enclosure to give a visual interface when commissioning or/and checking the status of the device.

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 

The equipments connected to the field transmitter WHA-UT-F7B1-0-PP-Z1-Ex2 must be compatible as regards to the intrinsic safety.

The equipment is intended to be used in an operating temperature range from -20°C to +60 °C.

For the risk from electrostatic discharge, the user will have to read the instructions.

 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx INE 09.0025X
 
Date of Issue:2010-08-27Issue No.: 0
 
Page 4 of 4
 
 
Additional information:
 

PARAMETERS RELATING TO THE SAFETY

Maximum input characteristics to the following terminals:

- Sensor terminals:

 Ui (V) Pi (mW) Ci (nF) Li (mH)
 3 50 72.6 negligible

- HART terminals:

 Ui (V) Pi (mW) Ci (nF) Li (mH)
 3 50 negligible negligible

Maximum output characteristics to the following terminals:

- Sensor terminals:

 Uo (V) Io (mA)Po (mW) Co (µF) Lo (mH)
 3.9 24.12 23.52100 63

- HART terminals:

 Uo (V) Io (mA)Po (mW) Co (µF) Lo (mH)
 3.9 10.410.1100 329

 

 
 








Copyright © IEC-IECEx 2016 , Geneva Switzerland. All rights reserved.