IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BVS 14.0032 issue No.: 0

Certificate history:

 
Status:
Current
 
Date of Issue:2014-04-04Page 1 of 3
 
 
Applicant:
Gönnheimer Elektronic GmbH
Dr.-Julius-Leber-Straße 2
67433 Neustadt an der Weinstraße
Germany
Equipment:Pressurized system type F850-SYST
 
Optional accessory:
 
Type of Protection:Equipment protection by intrinsic safety "i", Equipment protection by pressurized enclosure "p", Type of protection 'pD'

 Marking: Ex px IIC T3 - T6 Gb or Ex px [ib] IIC T3 - T6 Gb
Ex p III C T70°C - T195°C Db or Ex p [ib] III C T70°C - T195°C Db
 
 
Approved for issue on behalf of the IECEx
Certification Body:
H.-Ch. Simanski

 
Position:Head of Certification Body


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

  Certificate issued by:
DEKRA EXAM GmbH
Dinnendahlstrasse 9
44809 Bochum
Germany


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx BVS 14.0032
 
Date of Issue:2014-04-04Issue No.: 0
 
Page 2 of 3
  
Manufacturer:
Gönnheimer Elektronic GmbH
Dr.-Julius-Leber-Straße 2
67433 Neustadt an der Weinstraße
Germany


 
Additional Manufacturing location(s):

 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2011
Edition: 6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-11 : 2011
Edition: 6.0
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-2 : 2007-02
Edition: 5
Explosive Atmospheres - Part 2 Equipment protection by pressurized enclosure "p"
IEC 61241-4 : 2001
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 4: Type of protection 'pD'
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:

DE/BVS/ExTR14.0037/00


Quality Assessment Report:

DE/TUN/QAR10.0006/03


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx BVS 14.0032
 
Date of Issue:2014-04-04Issue No.: 0
 
Page 3 of 3
 
Schedule
 EQUIPMENT:
Equipment and systems covered by this certificate are as follows
 
 
Subject and Type
Pressurized system F850-SYST

Description
The pressurized system F850-SYST consist an enclosure in different enclosure versions for the installation of different electrical equipment. For the monitoring of purging and minimum overpressure the Pressurization system type F850S or type F860S (IECEX BVS 12.0033) resp. type FS870S (IECEx BVS 10.0095) can be used. The pressurized system can be extended with window, touchpad, keypad (in combination with a separately certified "Ex i" barrier for the touchpad/keypad circuits in type of protection "i" - intrinsic safety (IECEX TUN 13.0026X)) or separately certified components which can be used for mounting into the front panel of the enclosure.

Pararmeters
Electrical parameters:
Max. 690 V
Touchscreen Ex i- barrier: U0 = 5.4 V, I0 = 120 mA, P0 = 161 mW, C0 = 64 µH, L0 = 2 mH
Pneumatic parameters
Supply pressure 1 .. 25 bar
Service pressure 1 .. 6 bar
Minimum overpressure 0.8 mbar


 SPECIFIC CONDITIONS OF USE:   NO
 
 
 