IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BAS 08.0107X issue No.:4
 
Status:
Current
 
Date of Issue:2012-06-21 Page 1 of 4


    
Applicant:
Tyco Thermal Controls
Research Park Haasrode - Zone 2
Romeinsestraat 14
B-3001 Leuven
Belgium


 
Electrical Apparatus:The Compression Ring Type Cable Glands
Optional accessory:


 
Type of Protection:Ex d, Ex tD


 
Marking: Ex d IIC Ex tD A21 IP66 (- 60°C ≤ ta ≤ + 250°C)
 
Approved for issue on behalf of the IECEx
Certification Body:
R S Sinclair

 
Position:General Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Baseefa
Rockhead Business Park
Staden Lane
Buxton
Derbyshire
SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 08.0107X
 
Date of Issue:2012-06-21Issue No.: 4
 
Page 2 of 4
 
 Manufacturer:
Tyco Thermal Controls
Research Park Haasrode - Zone 2
Romeinsestraat 14
B-3001 Leuven
Belgium


 
 Additional Manufacturing location(s):
Thermocoax Isopad GmbH
Englerstrasse 11
Heidelberg D-69126
Germany
Tyco Thermal Controls (Canada) Limited
250 West Street
Trenton
Ontario
K8V 5S2
Canada
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-1 : 2007-04
Edition: 6
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 61241-0 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
IEC 61241-1 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 1: Protection by enclosures "tD"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/BAS/ExTR08.0224/00GB/BAS/ExTR11.0323/00GB/BAS/ExTR12.0139/00


Quality Assessment Report:

GB/BAS/QAR06.0036/03GB/BAS/QAR07.0053/02GB/BAS/QAR09.0003/02


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 08.0107X
 
Date of Issue:2012-06-21Issue No.: 4
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 
The cable glands each comprise a threaded gland body, a compression ring and a back-nut all manufactured in either brass or stainless steel.

The glands are manufactured to fit a range of propriety mineral insulated metal sheathed cables of sizes ranging from 5mm to 26mm diameter.

Guidance on the selection of appropriate gland sizes is included in the manufacturer’s instructions

The entry threads provided on the gland body may be M20, M25, M32 or M40 or ½”, ¾”, 1” and 1 ¼” NPT.

 

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 
1. When the gland is used for dust protection, the entry thread shall be suitably sealed, in accordance with IEC 60079‑14, to maintain the ingress protection rating of the associated enclosure.

2. If these glands are to be used on metal sheathed heater cables, the gland shall only be fitted on the cold lead in section of the cable.

3. Gland parts are not interchangeable and different cable sizes or gland materials should not be mixed.

4. These glands are considered suitable over the temperature range -60°C to +250°C.
 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 08.0107X
 
Date of Issue:2012-06-21Issue No.: 4
 
Page 4 of 4
 
 
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 
Variation 4.1

This issue permits existing information (for example on Schedule Drawings) to be replaced by the revised certificate holders name and address. No other changes may be made to the certified design
 
 








Copyright © IEC-IECEx 2013 , Geneva Switzerland. All rights reserved.