IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BAS 08.0047X issue No.:3
 
Status:
Current
 
Date of Issue:2012-03-29 Page 1 of 4


    
Applicant:
Tyco Thermal Controls
Research Park Haasrode - Zone 2
Romeinsestraat 14
B-3001 Leuven
Belgium


 
Electrical Apparatus:DigiTrace NGC-20-CL-E Heat-Tracing Temperature Control Unit
Optional accessory:


 
Type of Protection:Increased Safety, Encapsulation, Intrinsic Safety.


 
Marking: Gb Ex e mb ib IIC T5 (-40°C ≤ Ta ≤ +50°C)
Db Ex tD A21 IP66 T95°C
 
Approved for issue on behalf of the IECEx
Certification Body:
R S Sinclair

 
Position:General Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Baseefa
Rockhead Business Park
Staden Lane
Buxton
Derbyshire
SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 08.0047X
 
Date of Issue:2012-03-29Issue No.: 3
 
Page 2 of 4
 
 Manufacturer:
Tyco Thermal Controls
Research Park Haasrode - Zone 2
Romeinsestraat 14
B-3001 Leuven
Belgium


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-18 : 2004
Edition: 2.0
Electrical apparatus for explosive gas atmospheres - Part 18: Construction, test and marking of type of protection encapsulation 'm' electrical apparatus
IEC 60079-26 : 2006
Edition: 2
Explosive atmospheres - Part 26: Equipment with equipment protection level (EPL) Ga
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
IEC 61241-0 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
IEC 61241-1 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 1: Protection by enclosures "tD"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/BAS/ExTR08.0090/00GB/BAS/ExTR08.0091/00GB/BAS/ExTR09.0207/00GB/BAS/ExTR10.0095/00GB/BAS/ExTR12.0006/00


Quality Assessment Report:

GB/BAS/QAR07.0053/02


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 08.0047X
 
Date of Issue:2012-03-29Issue No.: 3
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

The DigiTrace NGC-20-CL-E Heat-Tracing Temperature Control Unit with Intelligent Safety Limiter, rated at 100V to 250V and up to 25A, comprises a plastic enclosure into which are encapsulated a number of printed circuit boards. Termination facilities are provided within the enclosure, above the level of the encapsulation, for the connection of power supply, external RTDs, alarm and data transmission facilities.

The encapsulated parts are divided into intrinsically safe and non-intrinsically safe printed circuit boards, with correspondingly segregated Ex ib and Exe termination facilities above the encapsulant.

Internal connections provided from the encapsulated printed circuit boards for three external resistance temperature detectors (RTDs), are made to Ex ib (RTD) terminals situated at the other side of the enclosure, and are segregated from the non-intrinsically safe terminals. Internal connections from the encapsulated printed circuit boards supply a seven segment LED display, five indicator LEDs and two internal push button switches, all mounted on a separate unencapsulated display printed circuit board behind a window in the lid of the enclosure. A common Earth Terminal is provided adjacent to the Ex ib (RTD) terminals for the termination of cable screens.

External connection is provided via cable entry holes, which enter the enclosure above the level of the encapsulation. Internal and external earthing facilities are provided. For Safety Parameters, see Annex.

The safety temperature limiter function of the DigiTrace NGC-20-CL-E meets the requirements of IEC 61508-1:1998 and IEC 61508-2:2003, Certificate Number Baseefa08SR0134.

Variation 0.1

Omission of the safety temperature limiter function and associated circuitry to form the DigiTrace NGC-20-C-E Heat-Tracing Temperature Control Unit.

The temperature control function of the DigiTrace NGC-20-C-E has not been assessed to the requirements of IEC 61508-1:1998 and IEC 61508-2:2003

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 

1.  Cable entry devices shall be suitably certified and maintain the IP66 minimum of the enclosure. Unused cable entries must be filled with suitably certified stopping plugs.
2.  Not more than one single or multiple strand wiring lead shall be connected into either side of the terminals.
3. Leads connected to the terminals shall be insulated for the appropriate voltage and this insulation shall extend to within 1mm of the metal of the terminal throat.
4. When used in dust atmospheres any dust layers occurring shall have a maximum depth of no greater than 50mm.
5. The max permitted current of the Non IS alarm contacts is 3A.
6. The earth pillar adjacent to the RTD connectors must be used only for RTD cable screens.
7. The external RTDs must be capable of withstanding a 500V test to earth.

 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 08.0047X
 
Date of Issue:2012-03-29Issue No.: 3
 
Page 4 of 4
 
 
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 
Variation 3.1

To permit the option of the local connection of 100 Ohm, 20%, 0.25W insulated resistors, replacing any of the RTD inputs, on the DigiTrace NGC-20-CL-E or NGC-20-C-E Heat-Tracing Temperature Control Units.
  
 ExTR:  GB/BAS/ExTR12.0006/00 File Reference:   12/0015
 
 
 








Copyright © IEC-IECEx 2013 , Geneva Switzerland. All rights reserved.