IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BAS 08.0114X issue No.:2
 
Status:
Current
 
Date of Issue:2012-03-14 Page 1 of 4


    
Applicant:
Hawke International
A Division of Hubbell Limited
A Member of the Hubbell Group of Companies
Oxford Street West
Ashton-under-Lyne
Lancashire
OL7 0NA
United Kingdom


 
Electrical Apparatus:Type 453UNIV Group 1 Cable Gland
Optional accessory:


 
Type of Protection:Ex d, Ex e


 
Marking: Ex d I Ex e I IP66 (-60°C ≤ ta ≤ +80°C)
 
Approved for issue on behalf of the IECEx
Certification Body:
R S Sinclair

 
Position:General Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Baseefa
Rockhead Business Park
Staden Lane
Buxton
Derbyshire
SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 08.0114X
 
Date of Issue:2012-03-14Issue No.: 2
 
Page 2 of 4
 
 Manufacturer:
Hawke International
A Division of Hubbell Limited
A Member of the Hubbell Group of Companies
Oxford Street West
Ashton-under-Lyne
Lancashire
OL7 0NA
United Kingdom


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2007-10
Edition: 5
Explosive atmospheres - Part 0:Equipment - General requirements
IEC 60079-1 : 2007-04
Edition: 6
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/BAS/ExTR08.0231/00GB/BAS/ExTR10.0287/00GB/BAS/ExTR11.0274/00


Quality Assessment Report:

GB/BAS/QAR06.0061/02


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 08.0114X
 
Date of Issue:2012-03-14Issue No.: 2
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 
The Type 453 Universal Cable Gland may be manufactured in brass or stainless steel and is intended for use with an effectively filled and circular armoured steel basket weave armoured or braided (screened) cable and comprises the following components:

a.             An entry component, in the size range Os to F (M20 to M75)
b.             A combined silicone inner seal, polymer support ring and metallic armour clamping cone.
c.             A reversible armour clamping ring.
d.             A middle nut.
e.             An outer seal assembly (sleeve seal and support ring).
f.              A back nut.

These glands may be supplied with specified alternative entry thread forms

 

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 
1.  These glands are suitable for use within an operating temperature range of -60°C to +80°C.

2.  When the gland is used for increased safety protection, the entry thread shall be suitably sealed (in accordance with IEC 60079-14) to maintain the ingress protection rating of the associated enclosure

3.  When used with steel basket weave armour or braided (screened) cable the basket weave armour or braid is unable to carry the cable load without fracture therefore the cable must be clamped and cleated to prevent pulling on the cable being transmitted to the cable terminations.    

 

 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 08.0114X
 
Date of Issue:2012-03-14Issue No.: 2
 
Page 4 of 4
 
 
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 
Variant 2.1

To allow the replacement of the 7o armour clamping components with 5o armour clamping components on gland sizes Os O and A,

Variant 2.2

The introduction of a range of dedicated reversible armour clamping rings in this form the UNIV stamping will be followed by DED and  a W, X, Y or Z to indicate the type  of armour that may be fitted
  
ExTR:  GB/BAS/ExTR011.0274/00 held with IEC Ex BAS.06.0013XFile Reference 11/0741 and 11/0943
 
 
 








Copyright © IEC-IECEx 2013 , Geneva Switzerland. All rights reserved.