IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx SIQ 12.0001X issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2012-02-29 Page 1 of 3


    
Applicant:
Bartec Varnost d.o.o.
Cesta 9. avgusta 59
SI-1410 Zagorje ob Savi
Slovenia


 
Electrical Apparatus:Transformer, type TSV-3 Tr* **
Optional accessory:


 
Type of Protection:Flameproof enclosure, Increased safety, Intrinsic safety


 
Marking: Ex de [ia Ma]  I Mb
 
Approved for issue on behalf of the IECEx
Certification Body:
Igor Likar

 
Position:Managing Director


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Slovenian Institute of Quality and Metrology (SIQ)
Trzaska cesta 2
SI-1000 Ljubljana
Slovenia


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIQ 12.0001X
 
Date of Issue:2012-02-29Issue No.: 0
 
Page 2 of 3
 
 Manufacturer:
Bartec Varnost d.o.o.
Cesta 9. avgusta 59
SI-1410 Zagorje ob Savi
Slovenia


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2007-10
Edition: 5
Explosive atmospheres - Part 0:Equipment - General requirements
IEC 60079-1 : 2007-04
Edition: 6
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
SI/SIQ/ExTR12.0001/00


Quality Assessment Report:

SI/SIQ/QAR11.0003/00


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIQ 12.0001X
 
Date of Issue:2012-02-29Issue No.: 0
 
Page 3 of 3
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

Transformer is intended for use in underground mines and is assembled from empty enclosure in type of protection flameproof enclosure from manufacturer Bartec Varnost d.o.o. type TSV-3 with component certificate SIQ 11 ATEX 171U and two enclosures in type of protection increased safety from manufacturer Bartec Varnost d.o.o. types PV-3 or PV-2 with component certificate OBAC 06 ATEX 454U, one mounted on the top of the flameproof enclosure and one on the bottom of the flameproof enclosure.In the TSV-3 enclosure cover switch type VN 32-XF-X-XX-X, main transformer type KDV/4, supply transformer type ET1-T, equipment for control of isolation of output circuit from manufacturer Bartec Polska Sp. z o.o. type ER100im with component certificate OBAC 06 ATEX 059U, isolating amplifier1 for remote switching on or off of the transformer from manufacturer Schuhmann GmbH & Co. KG type TSV3-Ex-R with certificate TÜV 07 ATEX 553613 and protection equipment are mounted.Passage of conductors out of flameproof enclosure is provided with line bushings type TOS5 25 A from manufacturer Bartec Varnost d.o.o. with component certificate PTB 04 ATEX 1099 U and with multicore line bushings type 07-91**-****/**** from manufacturer Bartec GmbH with component certificate PTB 97 ATEX 1047 U.

In the enclosures types PV-3 or PV-2 connection terminals from manufacturer WAGO Kontakttechnik GmbH with component certificate PTB 00 ATEX 3110 U, switch module from manufacturer CEAG Sicherheitstechnik GmbH with component certificate PTB 97 ATEX 1081 U and light modules from manufacturer R. STAHL Schaltgeräte GmbH with component certificate PTB 01 ATEX 1160 U are mounted. For cable entries cable glands from manufacturer El.-Ap. Elektro-Apparate Gothe & Co. GmbH with certificate IBExU01ATEX1013 X are mounted in the walls of enclosures.

1  Instead of isolating amplifier for remote powering on or off of the transformer from manufacturer Schuhmann GmbH & Co. KG type TSV3-Ex-R with certificate TÜV 07 ATEX 553613 isolating amplifier from manufacturer Hans Turck GmbH & Co. KG type MS13-22EX0-R with certificate DMT 01 ATEX E 119 can be used.

 

Technical data 

 Allowed ambient temperature is from -20°C to +40°C2.

 

For type key see Annex. 

 

2  If isolating amplifier from manufacturer Hans Turck GmbH & Co. KG type MS13-22EX0-R with certificate DMT 01 ATEX E 119 is used, allowed ambient temperature is from -20°C to +34°C.

 
 
CONDITIONS OF CERTIFICATION: YES as shown below:
 

-  Repair on flameproof joints may only be performed in accordance with the manufacturer's design specifications. Repair on the basis of the values in tables 1 and 2 of IEC 60079-1:2007 is not accepted.

 

-  Before opening of the flameproof enclosure transformer has to be switched off with remote control.

 

-  If the unit for remote control is installed in the hazardous area this unit has to be explosion protected.

 

-  If isolating amplifier from manufacturer Hans Turck GmbH & Co. KG type MS13-22EX0-R with certificate DMT 01 ATEX E 119 is used, allowed ambient temperature is from -20°C to +34°C, which has to be stated on the nameplate of the equipment.

 
 







Copyright © IEC-IECEx 2013 , Geneva Switzerland. All rights reserved.