Certificate No.:
IECEx BAS 04.0016 issue No.:7
 
Status:
Current
 
Date of Issue:2015-10-16 Page 1 of 4


    
Applicant:
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
Equipment:KFD2-STC(V)4-Ex1(.2O)... Smart Transmitter Isolator
Optional accessory:


 
Type of Protection:Intrinsic Safety


 
Marking:

[Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
-20°C ≤ Ta ≤ +60°C

 
Approved for issue on behalf of the IECEx
Certification Body:
R S Sinclair

 
Position:Technical Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
SGS Baseefa Limited
Rockhead Business Park
Staden Lane
Buxton
Derbyshire
SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 04.0016
 
Date of Issue:2015-10-16Issue No.: 7
 
Page 2 of 4
 
 Manufacturer:
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
 Additional Manufacturing location(s):
Pepperl + Fuchs PTE LTD
P + F Building
18 Ayer Rajah Crescent
SINGAPORE 139942
Singapore
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2011
Edition: 6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-11 : 2011
Edition: 6.0
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
IECEx ATR:File Reference:
GB/BAS/ExTR10.0301/00   10/0923  
GB/BAS/ExTR14.0292/00   14/0400  
GB/BAS/ExTR15.0306/00   15/0759  


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 04.0016
 
Date of Issue:2015-10-16Issue No.: 7
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 
The KFD2-STC(V)4-Ex1(.2O)... Smart Transmitter Isolator is a designed to provide galvanic isolation between intrinsically safe circuits in a hazardous area and unspecified associated apparatus in a non-hazardous area and limit the voltage and current into the hazardous area to intrinsically safe levels.

The apparatus comprises a number of electrical components, including transformers, fuses, resistors and zener diodes, all mounted on a single printed circuit board and housed within a plastic enclosure fitted with terminals for external connections.

The use of 'C' or 'V' in the type description specifies Current source / sink or Voltage respectively.

Options following 'Ex1' in the type description are:

 

.2O       (Dual non-hazardous area output)

 

-Y…     (Current sink - used with 'C')     

 

-1          (5 Volt - used with 'V')

 

-2          (10 Volt - used with 'V')


The apparatus is designed to operate from a d.c. supply of up to 35V on terminals 7 to 12, 14 and 15, and power rail connector terminals 1 and 2. The segregation of the hazardous area circuits meets the requirements for 250V.

For electrical data see Additional information.
 
CONDITIONS OF CERTIFICATION: NO
 
 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 04.0016
 
Date of Issue:2015-10-16Issue No.: 7
 
Page 4 of 4
 
 
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 

Variation 7.1

To permit the use of alternative fuses.

 ExTR:  GB/BAS/ExTR15.0306/00