IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BKI 04.0002 issue No.: 0
 
Status:
Current
 
Date of Issue:2004-12-01Page 1 of 3
 
 
Applicant:
Cooper Crouse-Hinds GmbH previously CEAG Sicherheitstechnik GmbH
Neuer Weg Nord 49
D-69412 Eberbach, Germany
Germany
Equipment:Plug and socket device, Typ GHG 51. ....R....
 
Optional accessory:
 
Type of Protection:General requirements, Flameproof enclosures, Increased safety, Intrinsic safety

 Marking: Ex ed [ia] IIC T6 or T5
-55 °C ≤ Tamb ≤ +55 °C
 
 
Approved for issue on behalf of the IECEx
Certification Body:
János HANKÓ

 
Position:Director


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

  Certificate issued by:
Testing Station for Explosion Proof Equipment
H 1037 BUDAPEST
MIKOVINY S.u. 2-4
Hungary


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx BKI 04.0002
 
Date of Issue:2004-12-01Issue No.: 0
 
Page 2 of 3
  
Manufacturer:
Cooper Crouse-Hinds GmbH previously CEAG Sicherheitstechnik GmbH
Neuer Weg Nord 49
D-69412 Eberbach, Germany
Germany


 
Additional Manufacturing location(s):

 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2000
Edition: 3.1
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-1 : 2001
Edition: 4
Electrical apparatus for explosive gas atmospheres - Part 1: Flameproof enclosures 'd'
IEC 60079-11 : 1999
Edition: 4
Electrical apparatus for explosive gas atmospheres - Part 11: Intrinsic safety 'i'
IEC 60079-7 : 2001
Edition: 3
Electrical apparatus for explosive gas atmospheres - Part 7: Increased safety 'e'
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
IECEx ATR:File Reference:
HU/BKI/04/P-002-04/1-1, HU/BKI/04/P-002-04/1-2   P-002-04/1  
HU/BKI/04/P-002-04/1-3, HU/BKI/04/P-002-04/1-4    
   


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx BKI 04.0002
 
Date of Issue:2004-12-01Issue No.: 0
 
Page 3 of 3
 
Schedule
 EQUIPMENT:
Equipment and systems covered by this certificate are as follows
 
 
The type GHG 51 The type GHG 51. ….R…. plug-and-socket device serves to connect portable electrical apparatus or to make connections in potentially explosive atmospheres.

 

The following variant is permissible: transformer plugs (isolating transformer, class of protection II).

 

Extra-low-voltage version: type GHG 513….R….

 

The wall mounting socket outlet, type 511.4..R…. may also be provided with an auxiliary switch for operation with an intrinsically safe circuit.

 

Plug connector

The plug-and-socket device, type GHG 511….R…., is supplemented by plug connector GHG 531.7..V…. (old design) of plug-and-socket device GHG 531….V…. (old Certificate of Conformity PTB No. Ex-85.B.1115), which has the same explosion-proof characteristics.

 

The plug-and-socket device may also be used in the hazardous area „dust”.

 

The plug-and-socket device, type GHG 51. ….R…., may also be manufactured with the different modifications.

Rated voltage … up to                       690 V

Rated current … max.                       16/20 A

Utilization category                            AC-3

 

Transformer plug

Rated voltage, primary …                 up to      250 V

Raged voltage, secondary …           up to      42 V

Power consumption                         max        65 VA

Miniatur fuse …                                  0,5 A

Temperature class                            T5

 

The plug-and-socket device type GHG 513….R…. is supplemented by an extra-low-voltage version

Rated insulating voltage …                              up to      60 V

Rated voltage …                                                 up to      50 V        50 V        50 V

Rated current …                                                 max        16 A        16 A        10 A

Utilization category …                                       AC-3       DC-1       DC-11

 

Rated frequency …                                            up to                      400 Hz

Rated cross-section                                         2,5 mm2 or 4 mm2

                                                                                                                                                                           

Ingress protection: IP66 by IEC 60529


 



 SPECIFIC CONDITIONS OF USE:   NO
 
 
 




Copyright © IEC-IECEx 2019 , Geneva Switzerland. All rights reserved.