IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx SIR 06.0106 issue No.:6
 
Status:
Current
 
Date of Issue:2013-07-15 Page 1 of 4


    
Applicant:
Pepperl+Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
Equipment:GL Range of Terminal Boxes
Optional accessory:


 
Type of Protection:Intrinsically Safe, Increased safety and Dust


 
Marking: Ex ia IIC T* Ga (Ta = – **°C to + **°C)
Ex e II T* Gb (Ta = – **°C to + **°C)
Ex tb IIIC T# °C Db IP6X (Ta = – **°C to + **°C)
The temperature classifications and ambient temperature range are as follows:
*T6, #T80°C (Ta = -40°C or – 50°C to + 40°C) or
*T6, #T80°C (Ta = -40°C or -50°C to +50°C) or
*T5, #T95°C (Ta = -40°C or – 50°C to + 55°C) or
*T4, #T130°C (Ta = -40°C – 50°C to + 60°C)
 
Approved for issue on behalf of the IECEx
Certification Body:
A C Smith

 
Position:Certification Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
SIRA Certification Service
Rake Lane
Eccleston
Chester
CH4 9JN
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 06.0106
 
Date of Issue:2013-07-15Issue No.: 6
 
Page 2 of 4
 
 Manufacturer:
Pepperl+Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
 Additional Manufacturing location(s):

Refer to the annexe for alternative manufacturing locations
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-0 : 2007-10
Edition: 5
Explosive atmospheres - Part 0:Equipment - General requirements
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-31 : 2008
Edition: 1
Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure 't'
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/SIR/ExTR07.0070/00GB/SIR/ExTR09.0193/00GB/SIR/ExTR10.0193/00GB/SIR/ExTR10.0194/00GB/SIR/ExTR11.0307/00GB/SIR/ExTR12.0056/00GB/SIR/ExTR12.0266/00GB/SIR/ExTR13.0206/00


Quality Assessment Report:

AU/TSA/QAR06.0004/05DE/PTB/QAR06.0008/02DE/PTB/QAR06.0008/03DE/PTB/QAR06.0008/04DE/PTB/QAR06.0015/01DE/PTB/QAR06.0015/02DE/PTB/QAR06.0015/03DE/PTB/QAR10.0008/00DE/PTB/QAR10.0008/01GB/SIR/QAR07.0004/00GB/SIR/QAR07.0004/01US/UL/QAR07.0005/03US/UL/QAR07.0005/04US/UL/QAR07.0005/06


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 06.0106
 
Date of Issue:2013-07-15Issue No.: 6
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 
The GL Range of terminal enclosures comprises a range of glass fibre reinforced polyester enclosures to IECEx SIR06.0105U, and fitted with specified terminals as indicated in Table 2 in the Annexe. The GL Range is available in 14 sizes designated GL1 to GL14, the maximum power dissipation for each enclosure size, temperature classification, and ambient temperature range is in Table 1 in the Annexe, for use in dust atmospheres, the enclosures are marked T80°C, T95°C or T130°C.
 
SPECIFIC CONDITIONS OF USE: NO
 
 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 06.0106
 
Date of Issue:2013-07-15Issue No.: 6
 
Page 4 of 4
 
 
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 

Issue 1 – this Issue introduced the following changes:

1.An alternative, new method of attaching Certification labels was approved; this uses a screw, nut and silicone sealant assembly.
2.The marking section was corrected, this includes amending the ambient temperature limits to agree with those quoted in the table of maximum power dissipations, in addition, this table was modified to correct a typographical error.
3.Update to standards. IEC 60079-0:2004 included for dated reference in IEC 60079-11:2007.
Issue 2 – this Issue introduced the following changes:
1The company name and address change was changed and alternative manufacturing sites were recognised
2The use of alternative label materials was approved.
3.The addition of a Datamatrix code on the label was endorsed
Issue 3 – this Issue introduced the following changes:
1Actuators, indicator lamps, potentiometers and switch modules manufactured by Bartec GmbH certified under IECEx PTB 08.0037U, IECEx PTB 10.0014U, IECEx PTB 10.0017U and IECEx PTB 07.0046U were approved to be fitted within the enclosures
2Recognition of reduced assigned power ratings applied when the switch modules manufactured by Bartec GmBH certified under IECEx PTB 07.0046U is fitted was approved. The reduced maximum power ratings for the enclosures.  The reduced maximum power ratings for the enclosures, , calculated in accordance with IEC 60079‑7:2006 Ed 4, Annex E, are shown in the annexe.
Issue 4 – this Issue introduced the following change:
1The introduction of a new manufacturing location in Twinsburg Ohio.
Issue 5 – this Issue introduced the following changes:
1.The introduction of the following alternative manufacturing locations was approved.
 Pepperl+Fuchs Inc., 4333 West Sam Houston Parkway, North Suite 150, Houston, Texas 77043, USA and Pepperl+Fuchs (Australia) Pty Ltd, 131-149 Link Drive, Campbellfield, Victoria, 3061, Australia
 
 