IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx SIR 09.0056X issue No.:1
 
Status:
Current
 
Date of Issue:2009-11-03 Page 1 of 4


    
Applicant:
ABTECH limited
Sanderson Street
Lower don Valley
Sheffield S9 2UA
United Kingdom


 
Electrical Apparatus:BPG Control Stations / ABCS1x
Optional accessory:


 
Type of Protection:Increased Safety and Dust


 
Marking: Ex e II T4 or Ex de IIC
Ex tD A21 IP65 or IP66 T130°C
Ta = -20°C to +55°C or -20°C to +40°C
 
Approved for issue on behalf of the IECEx
Certification Body:
C Ellaby

 
Position:Certification Officer


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
SIRA Certification Service
Rake Lane
Eccleston
Chester
CH4 9JN
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 09.0056X
 
Date of Issue:2009-11-03Issue No.: 1
 
Page 2 of 4
 
 Manufacturer:
ABTECH limited
Sanderson Street
Lower don Valley
Sheffield S9 2UA
United Kingdom


 
 Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-1 : 2003
Edition: 5
Electrical apparatus for explosive gas atmospheres - Part 1: Flameproof enclosure 'd'
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
IEC 61241-0 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
IEC 61241-1 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 1: Protection by enclosures "tD"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/SIR/ExTR09.0064/01


Quality Assessment Report:

GB/SIR/QAR06.0046/00GB/SIR/QAR06.0046/01


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 09.0056X
 
Date of Issue:2009-11-03Issue No.: 1
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

The BPG range of Control Stations comprise of polyester enclosures that are fitted with an arrangement of IECEx certified ammeters, switches, signal lamps and terminals.  All enclosures are fitted with gaskets of substantially round cross section, closed cell polychloroprene or closed cell silicone rubber.  The enclosure lid can be populated with switch operators, lamp bezels or 4mm thick glass windows as specified on the associated certification drawings.  Tapped or clearance hole entries may be provided through the side walls or the rear of the box.  When unused the entries will be blanked off with IECEx metal blanking plugs and sealing washers or O-rings suitable for the ingress protection provided by the enclosure.

 
See Annex for the range, power dissipation and permitted components
 
 
CONDITIONS OF CERTIFICATION: YES as shown below:
 

1.

The enclosure is non-conducting and may generate an ignition-capable level of electrostatic charges under certain extreme conditions.  The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions (such as high-pressure steam), which might cause a build-up of electrostatic charges on non-conducting surfaces.  Additionally, cleaning of the equipment should be done only with a damp cloth.
 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 09.0056X
 
Date of Issue:2009-11-03Issue No.: 1
 
Page 4 of 4
 
 
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 

Issue 1 – this Issue introduced the following changes:

1

Report number R51A20310B replaced R51A20310A.

 
 