IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx SIR 13.0021 issue No.:0
 
Status:
Current
 
Date of Issue:2013-04-17 Page 1 of 3


    
Applicant:
Pepperl+Fuchs GmbH
Lilienthalstrasse 200
38307 Mannheim
Germany


 
Equipment:CJB Control Junction Boxes
Optional accessory:


 
Type of Protection:Flameproof, Increased Safety and Dust


 
Marking:
Ex d e IIC T* Gb* T4 or T5 for gas applications, refer to product description.
Ex tb IIIC T* Db* T95°C or T130°C for dust application, refer to product description.
(-40°C to +55°C)
 
Approved for issue on behalf of the IECEx
Certification Body:
C Ellaby

 
Position:Deputy Certification Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
SIRA Certification Service
Rake Lane
Eccleston
Chester
CH4 9JN
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 13.0021
 
Date of Issue:2013-04-17Issue No.: 0
 
Page 2 of 3
 
 Manufacturer:
Pepperl+Fuchs Manufacturing UK Ltd.
Unit 8, The Woods Bank Estate, Woden Road West, Wednesbury, West Midlands WS10 7SU, UK
United Kingdom


 
 Additional Manufacturing location(s):

Refer to Certificate Annexe for additional manufacturing sites.
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2011
Edition: 6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-1 : 2007-04
Edition: 6
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 60079-31 : 2008
Edition: 1
Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure 't'
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/SIR/ExTR13.0094/00


Quality Assessment Report:

DE/PTB/QAR06.0007/03DE/PTB/QAR06.0008/05DE/PTB/QAR06.0015/03DE/PTB/QAR10.0008/01US/UL/QAR07.0005/05


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 13.0021
 
Date of Issue:2013-04-17Issue No.: 0
 
Page 3 of 3
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 
The CJB range of Control Junction Boxes utilise either the XL and FXL types of fabricated mild steel or stainless steel enclosures, certified under IECEx SIR 06.0073U or the GL types, which are moulded from carbon loaded glass reinforced polyester certified under IECEx SIR 06.0105U. All enclosures are manufactured by Pepperl+Fuchs. The enclosure sizes are detailed in the certificate Annexe.
The enclosures may be fitted with an arrangement of ATEX/IECEx certified ammeters, switch modules, signal lamps, signal lamps with contacts, operator heads, potentiometers and terminals. The permitted devices are detailed in the certificate Annexe.
The total maximum power dissipation values have been assigned based on internal temperature rises of 5 K, 10 K and 15 K to account for the limiting temperatures of the different devices that may be installed; the maximum power dissipation values assigned for each enclosure size shall not be exceeded and are detailed in the certificate Annexe.
Tapped or clearance hole entries may be provided through the side walls or the rear of the enclosures, as permitted by the individual enclosure certification, for the use of suitably certified Ex e IIC Gb/Ex tb IIIC Db (minimum) entry devices suitable for an ambient range as marked.
 
CONDITIONS OF CERTIFICATION: NO
 
 







Copyright © IEC-IECEx 2016 , Geneva Switzerland. All rights reserved.