IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx UL 08.0003X issue No.: 7
 
Status:
Current
 
Date of Issue:2016-04-17Page 1 of 4
 
 
Applicant:
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany
Equipment:Purge and Pressurization System, 6000 Series
 
Optional accessory:
 
Type of Protection:Flameproof "d", Intrinsically Safe "ib", Pressurization "px", Enclosure "tb"

 Marking:

Ex db ib [ib pxb] IIC T4 Gb/Ex ib tb [ib pxb] III C T60°C Db (Main Enclosure Alternate Housing)
Ex db [ib pxb] IIC T4 Gb/Ex tb [ib pxb] III C T80°C Db (Component Kit)
Ex ib [pxb] IIC T4 Gb (User Interface/ IS Interface Board/ IS Interface Board DIN Rail)
Ex ib IIC T4 Gb/ Ex ib III C T60°C Db (Accessory Enclosure)
Ex ib IIC T4 Gb (Temperature Hub)
Ex ib IIC T4 Gb/Ex ib III C T210°C Db (Temperature Sensor)

 
 
Approved for issue on behalf of the IECEx
Certification Body:
Lucy Frieders

 
Position:Staff Engineer


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

  Certificate issued by:
UL LLC
333 Pfingsten Road
Northbrook IL 60062-2096
United States of America


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx UL 08.0003X
 
Date of Issue:2016-04-17Issue No.: 7
 
Page 2 of 4
  
Manufacturer:
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
Additional Manufacturing location(s):
Pepperl + Fuchs Inc.
1600 Enterprise Parkway
Twinsburg, OH 44087
United States of America

 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2011
Edition: 6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-1 : 2007-04
Edition: 6
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 60079-11 : 2011
Edition: 6.0
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-2 : 2007-02
Edition: 5
Explosive Atmospheres - Part 2 Equipment protection by pressurized enclosure "p"
IEC 60079-2 : 2014-07
Edition: 6
Explosive atmospheres - Part 2: Equipment protection by pressurized enclosure "p"
IEC 60079-31 : 2008
Edition: 1
Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure 't'
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:

US/UL/ExTR14.0117/00


Quality Assessment Report:

DE/PTB/QAR06.0007/04US/UL/QAR07.0005/09


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx UL 08.0003X
 
Date of Issue:2016-04-17Issue No.: 7
 
Page 3 of 4
 
Schedule
 EQUIPMENT:
Equipment and systems covered by this certificate are as follows
 
 

The Model 6000 is a permanently installed purge and pressurization control system intended to provide ”pxb” purge and pressurization in accordance with IEC 60079-2. Instructions and markings are provided with the control system indicating how to install this device to the electrical enclosure to be purged and pressurized in accordance with IEC 60079-2.
The purge control enclosure is composed of stainless steel. It is comprised of a cover and body, power supply and main controller, user interface, vent (see IECEx UL 15.0147X for details), optional I.S.
Termination Board DIN mounted, optional temperature hub, and up to three temperature sensors when the temperature hub is provided. The power supply and main controller are housed in a flameproof (”db”) enclosure. The user interface, temperature hub, temperature sensors, and vent are intrinsically safe (”ib"). The control system enclosure contains the IS interface board, which has connection facilities for intrinsically safe circuits.
The IS interface board is provided with five connection facilities that have assigned entity parameters. The component kit is comprised of the power electronics, user interface, vent, optional bushing (wiring harness), optional temperature hub, and up to three temperature sensors when the temperature hub is provided.  The vent is separately certified.

See Annex for additional information.



 SPECIFIC CONDITIONS OF USE:   YES as shown below:
 
 

See Annex for Conditions of Certification.

 


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx UL 08.0003X
 
Date of Issue:2016-04-17Issue No.: 7
 
Page 4 of 4
 
 DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 
 

Issue 1: The revision includes the additon of the pressurization system component kit, Model 6000-XX-XX-XX-CK-XX.

Issue 2: Addition of intrinsically safe "ib", Temperature Module and Temperature Sensor.

Issue 3: The manfacturer has updated the gasket used on the main unit enclosure, two resistors within the intinsically safe circuits, the thickness of the material on the intrinsically safe wiring partition and the addition of an alternate material for intrisically safe wiring partition. Also, updated to IEC 60079-1 Edition 6 and IEC 60079-2 Edition 5.

Issue 4: Addition of dust certification to temperature sensors/Hub and updated IEC 60079-0 edition, alternate components, and IP66 enclosure rating.

Issue 5: Update to drawings regarding the IS Termination Board DIN Mounted, Model 6000-ISB-XX.

Issue 6: Removal of the SciCron Coating from the Keypad.

Issue 7: Updated standards and drawings.

 
 




Copyright © IEC-IECEx 2019 , Geneva Switzerland. All rights reserved.