IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BAS 05.0041 issue No.:1
 
Status:
Current
 
Date of Issue:2010-12-21 Page 1 of 4


    
Applicant:
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
Electrical Apparatus:Type KFD2-CD-Ex1.32-** Transformer Isolated Output Driver
Optional accessory:


 
Type of Protection:Intrinsic Safety


 
Marking: IECEx BAS 05.0041
[Zone 0] [Ex ia] IIC
[Ex ia] I
[Ex iaD]
-20C ≤ Ta ≤ +60C
 
Approved for issue on behalf of the IECEx
Certification Body:
R S Sinclair

 
Position:Managing Director


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Baseefa
Rockhead Business Park
Staden Lane
Buxton
Derbyshire
SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 05.0041
 
Date of Issue:2010-12-21Issue No.: 1
 
Page 2 of 4
 
 Manufacturer:
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
 Additional Manufacturing location(s):
Pepperl + Fuchs PTE LTD
P + F Building
18 Ayer Rajah Crescent
39942
Singapore
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-26 : 2004
Edition: 1
Electrical apparatus for explosve gas atmospheres - Part 26: Construction, test and marking of Group II Zone 0 electrical apparatus
IEC 61241-11 : 2005
Edition: 1
Electrical apparatus for use in the presence of combustible dusts - Part 11: Protection by intrinsic safety 'iD'
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
IECEx ATR:File Reference:
UK/BAS/04/0751   04/0751  
GB/BAS/ExTR10.0289/00   10/0767  
   


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 05.0041
 
Date of Issue:2010-12-21Issue No.: 1
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 
The Type KFD2-CD-Ex1.32-** Transformer Isolated Output Driver is a device designed to restrict the transfer of energy from unspecified non-hazardous area apparatus to intrinsically safe temperature sensors located in the hazardous area, and provide galvanic isolation between the hazardous and non-hazardous area circuits.

The Type KFD2-CD-Ex1.32-** Transformer Isolated Output Driver comprises a number of electrical components, including isolating transformers, fuses, resistors and zener diodes all mounted onto a single printed circuit board (PCB) and housed within a plastic enclosure with plug-in terminals.

The apparatus comes in various options which are identified by the **.
The option permits the unit to convert the input signal to output signal from current to current; current to voltage; voltage to current or voltage to voltage in any combination of the following voltage and current type:-
Output Current (** = 0 to 8): 0-20mA & 4-20mA
Output Voltage (** = 9 to 25): 0-5V, 1-5V, 0-10V & 2-10V

For apparatus parameters see data in the Annex. 
 
CONDITIONS OF CERTIFICATION: NO
 
 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 05.0041
 
Date of Issue:2010-12-21Issue No.: 1
 
Page 4 of 4
 
 
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 

Variation 1.1

To permit minor drawing changes that do not affect the original assessment.


Variation 1.2

To confirm that the equipment covered by this certificate has been reviewed against the requirements of IEC 60079-0: 2004 Ed 4 and IEC 60079-11: 2006 Ed 5 in respect of the differences from IEC 60079-0: 2000 Ed 3.1 and IEC 60079-11: 1999 and that none of these differences affect this equipment.

Variation 1.3

To confirm the current design has additionally been assessed for compliance with the requirements of Associated Apparatus to IEC 60079-26: 2004 Edition 1 and IEC 61241-11: 2005 Edition 1. The standards have been added to the list on page 2 and the markings revised on page 1 to: -

[Zone 0] [Ex ia] IIC
[Ex ia] I
[Ex iaD]
-20°C ≤ Ta ≤ +60°C

Variation 1.4

To record a change of formal address for applicant and manufacturer:

Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany

 ExTR:  GB/BAS/ExTR10.0289/00 File Reference:   10/0767
 
 