IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BAS 13.0043X issue No.:0
 
Status:
Current
 
Date of Issue:2013-12-12 Page 1 of 3


    
Applicant:
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
Electrical Apparatus:Transmitter Power Supply Type KCD2-STC-Ex1.2O
Optional accessory:


 
Type of Protection:Intrinsic Safety


 
Marking: [Ex ia Ga] IIC (-20°C ≤ Ta ≤ +60°C / +70°C)
[Ex ia Da] IIIC (-20°C ≤ Ta ≤ +60°C / +70°C)
[Ex ia Ma] I (-20°C ≤ Ta ≤ +60°C / +70°C)

 
Approved for issue on behalf of the IECEx
Certification Body:
R. S. Sinclair

 
Position:General Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
SGS Baseefa Limited
Rockhead Business Park
Staden Lane
Buxton
Derbyshire
SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 13.0043X
 
Date of Issue:2013-12-12Issue No.: 0
 
Page 2 of 3
 
 Manufacturer:
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
 Additional Manufacturing location(s):
Pepperl + Fuchs (Manufacturing) PTE LTD
18 Ayer Rajah Crescent
Singapore 139942
Singapore
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2011
Edition: 6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-11 : 2011
Edition: 6.0
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/BAS/ExTR13.0136/00


Quality Assessment Report:

DE/PTB/QAR06.0007/03DE/PTB/QAR06.0008/05


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 13.0043X
 
Date of Issue:2013-12-12Issue No.: 0
 
Page 3 of 3
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

The Transmitter Power Supply Type KCD2-STC-Ex1.2O* is designed to monitoring signals from equipment in a hazardous area to unspecified apparatus located in a non-hazardous area and communication signals in both directions. The hazardous area circuit is galvanically isolated from the non-hazardous area circuit using transformers and the voltage and current appearing at the hazardous area connectors are limited to intrinsically safe levels.

The Transmitter Power Supply KCD2-STC-Ex1.2O* comprises a number of electronic components including four isolating transformer, fuses, zener diodes and resistors all mounted on a single printed circuit board and housed in a plastic enclosure with plug-in terminals for hazardous and non-hazardous area connections. LED indication is provided for power-on status. 

The following variants are covered by this certificate:
KCD2-STC-Ex1.2O
KCD2-STC-Ex1.2O.ES
KCD2-STC-Ex1.2O.DE
KCD2-STV-Ex1.2O
KCD2-STV-Ex1.2O.ES
KCD2-STC-Ex1.2O(**)-Y1...n
KCD2-STV-Ex1.2O(**)-Y1...n

See Annex for electrical data.

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 

1. The KCD2-STC-Ex1.2O must be installed in a controlled environment with suitably reduced pollution.

 







Copyright © IEC-IECEx 2016 , Geneva Switzerland. All rights reserved.