IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BVS 07.0027X issue No.:3
 
Status:
Current
 
Date of Issue:2013-09-11 Page 1 of 4


    
Applicant:
G.M. International S.R.L.
Via San Fiorano 70
20058 Villasanta (MI)
Italy


 
Equipment:DIN Rail Isolator type D1****, PSD1001*
Optional accessory:


 
Type of Protection:Intrinsic safety "i", Construction, test and Marking of Type of Protection "n" electrical apparatus, Equipment with equipment protection level (EPL) Ga, Protection by intrinsic safety "iD"


 
Marking: Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I
 
Approved for issue on behalf of the IECEx
Certification Body:
Dr. F. Eickhoff

 
Position:Deputy Head of Certification Body


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
DEKRA EXAM GmbH
Dinnendahlstrasse 9
44809 Bochum
Germany


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BVS 07.0027X
 
Date of Issue:2013-09-11Issue No.: 3
 
Page 2 of 4
 
 Manufacturer:
G.M. International S.R.L.
Via San Fiorano 70
20058 Villasanta (MI)
Italy


 
 Additional Manufacturing location(s):

 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2011
Edition: 6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-11 : 2011
Edition: 6.0
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-15 : 2010
Edition: 4
Explosive atmospheres - Part 15: Equipment protection by type of protection "n"
IEC 60079-26 : 2006
Edition: 2
Explosive atmospheres - Part 26: Equipment with equipment protection level (EPL) Ga
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
DE/BVS/ExTR07.0033/03


Quality Assessment Report:

NO/DNV/QAR07.0005/04


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BVS 07.0027X
 
Date of Issue:2013-09-11Issue No.: 3
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 
Type Code
(No extension)

Details of change:
DIN Rail Isolators have been subjected to some minor changes not affecting IS parameters.
Ratings:
Parameters specified in previous issues 00, 01, 02 remain valid without change.
Lo, Co and Lo/Ro parameters specified for Group IIB in previous issues 00, 01, 02 apply in addition for Group IIIC.
 
SPECIFIC CONDITIONS OF USE: YES as shown below:
 
Special conditions for safe use (applicable if not covered by local installation rules) for issue 0 and 1
 
1. Group I application:
DIN Rail Isolators of type series D1**** / PSD1001* shall be installed outside the hazardous area or alternatively in an enclosure providing a suitable type of protection according to separate certification.
 
2. Group II application:
DIN Rail Isolators of type series D1**** / PSD1001* shall be installed outside the hazardous area or, (applies to models D1048S, D1048S-xxx, D1049S*, D1049S-xxx*, D1061S-077, D1061S-077/B only) - shall be mounted inside an enclosure, which is in accordance with EN 60079-15 in case of alternative installation in areas requiring EPL Gc equipment.
 
3. Group III application:
DIN Rail Isolators of type series D1**** / PSD1001* shall be installed outside the hazardous area or alternatively in an enclosure providing a suitable type of protection according to separate certification.
 
4. General:
The installation of DIN Rail Isolators of type series D1**** / PSD1001* shall be carried out in such a way that the clearances of un-insulated conductors of intrinsically safe circuits to grounded metal parts of the enclosure are at least 3 mm, and un-insulated conductors of non-intrinsically safe circuits of other apparatus are situated at least 50 mm from terminals for external intrinsically safe circuits, or are separated from them by an insulating barrier according to clause 6.2.1 of IEC 60079-11:2011.
 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BVS 07.0027X
 
Date of Issue:2013-09-11Issue No.: 3
 
Page 4 of 4
 
 
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 
DIN Rail Isolators have been subjected to some minor changes not affecting IS parameters.
 
 








Copyright © IEC-IECEx 2017 , Geneva Switzerland. All rights reserved.