Certificate No.:
IECEx BVS 11.0046X issue No.: 0
 
Status:
Current
 
Date of Issue:2011-05-31Page 1 of 4
 
 
Applicant:
Elmess Thermosystemtechnik GmbH & Co. KG
Nordallee 1
29525 Uelzen
Germany
Equipment:Heater type EH* ********-T*
 
Optional accessory:
 
Type of Protection:Equipment protection by flameproof enclosures "d", Equipment protection by increased safety "e", Protection by enclosures "tD"

 Marking: Ex e IIC T6-T1 resp. Ex e IIB T6-T1
or
Ex de IIC T6-T1 resp. Ex de IIB T6-T1
Ex tD A21 IP66 T80 °C -T440 °C
 
 
Approved for issue on behalf of the IECEx
Certification Body:
H.-Ch. Simanski

 
Position:Head of Certification Body


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

  Certificate issued by:
DEKRA EXAM GmbH
Dinnendahlstrasse 9
44809 Bochum
Germany


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx BVS 11.0046X
 
Date of Issue:2011-05-31Issue No.: 0
 
Page 2 of 4
  
Manufacturer:
Elmess Thermosystemtechnik GmbH & Co. KG
Nordallee 1
29525 Uelzen
Germany


 
Additional Manufacturing location(s):

 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-1 : 2007-04
Edition: 6
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
IEC 61241-0 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
IEC 61241-1 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 1: Protection by enclosures "tD"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:

DE/BVS/ExTR11.0066/00


Quality Assessment Report:

DE/TUN/QAR09.0007/00


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx BVS 11.0046X
 
Date of Issue:2011-05-31Issue No.: 0
 
Page 3 of 4
 
Schedule
 EQUIPMENT:
Equipment and systems covered by this certificate are as follows
 
 
 
Description
 
The heater type EH* ********-T* is used for a direct or an indirect heating of gases, liquids and solid bodies in areas endangered by explosive atmospheres for zone 1 and 2 respectively zone 21 and 22.
 
The electrical heater is suitable for a mounting into boxes, machines, tubes or canal systems.
 
The heater may only be used with safety systems. For example temperature-, flow-, level-, current- or insulation-control.
 
The heater consists of the a terminal box that could be designed in the type of protection flameproof enclosure or increased safety for use in areas endangered by gas or in type of protection “protection by enclosure” for use in areas endangered by dusts. Optionally the terminal boxes can already be certified as separate equipment. In this case the electrical and thermal ratings have to be taken into account.
 
Optionally a connection enclosure in type of protection increased safety or protection by enclosure can be installed directly below the terminal box. The connection between the two enclosures occurs with separately certified cable bushings that are suitable for this purpose. Alternatively the connection enclosure can be installed with a distance to the terminal box. In this case the connection between the two enclosures occurs with separately certified cable glands that are suitable for this purpose.
 
The connection box can optionally be filled up with sand or a potting compound.


 SPECIFIC CONDITIONS OF USE:   YES as shown below:
 
 
 
The temperature class and surface temperature, a monitoring unit (level, flow rate) if applicable and further operating conditions (ambient temperature range, self heating, conduction of heat, mounting orientation, etc.) have to be fixed with the testing of the complete heating construction.
 
The used safety devices for limiting the temperature, monitoring the flow rate and/or monitoring the level have to be suitable for this purpose and have to be certified.
 
The heater with flow rate monitoring may only be used when the flow rate is above the minimum flow rate that was basis for the temperature measurement.
 
The heater with level monitoring may only be used when the level is above the minimum level that was basis for the temperature measurement.
 
In case of medium temperatures at the outgoing part that were higher than the temperature class of the heater, the thermal isolation has to be taken into account for the explosion protection measure.
In addition to the surface temperature of the box, other parts (e.g. flange, nameplate, valves and accessories, etc.) that can be heated impermissible have to be part of the isolation or the thermal conductance have to be suppressed.
The thermal isolation has to prevent the migration of gases and vapours of the surrounding environment to the hot parts.
The thermal isolation is not part of this type examination.
 
The positioning of the temperature sensors for the temperature limiter has to be carried out in such a way, that a failure of one phase is included.
 
The conditions of safe use of the separately certified equipment / components have to be taken into account.
 


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx BVS 11.0046X
 
Date of Issue:2011-05-31Issue No.: 0
 
Page 4 of 4
 
 EQUIPMENT(continued):
 
 
 
Subject and type
 
Heater type EH*1) **2) ***3) *4) *5) *6)-T*7)
 
1) : Usable for heating medium
       F: fluids
       G: gases / air
       K: heating element encapsulated with solid body
 
2) : Design related to intended purpose
 
3) : Type of separately certified flameproof terminal box
      M0, A00, A0, B1, B2, B3, C4, C5, C7, G5
 
4) : Type of enclosure material (optional)
 
5) : D: Direct cable entry into the separately certified flameproof terminal box (optional)
 
6) : Index number for rated power
 
7) : Surface temperature
      The surface temperature will be determined by the notified body or according to the process
      instructions by the manufacturer
 

 
Ratings
 
Main circuit:
Rated voltage max.           800 V
Rated current max.           630 A
Size of conductor max.     400 mm²
 
Control circuit:
Rated voltage max.          440 VAC / 250 VDC
Rated current max.          16 A / 0.25 A
 
Ambient temperature range                                                                     -60 °C up to +60 °C
 
Maximum temperature range for end caps of the heating elements       -60 °C up to +85 °C
 
Maximum temperature range for the sealing of the connection box        -60 °C up to +80 °C
 
The temperature class and maximum surface temperature of the heater will be determined with
consideration to local circumstances by the manufacturer according to the process instructions
or by a notified body.
 
 