IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx CES 10.0011 issue No.: 0

Certificate history:

 
Status:
Current
 
Date of Issue:2010-07-12Page 1 of 4
 
 
Applicant:
Pepperl + Fuchs GmbH
Lilienthalstraße 200,
68307 Mannheim
Germany
Equipment:Galvanically isolated barrier type: HiD2025, HiD2025SK, HiD2026 and HiD2026SK
 
Optional accessory:
 
Type of Protection:Intrinsic Safety "ia"; dust "iD"

 Marking:

[Zone 0] [Ex ia] IIC
[Ex iaD]

 
 
Approved for issue on behalf of the IECEx
Certification Body:
M. Balaz

 
Position:Head of IECEx CB


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

  Certificate issued by:
CESI
Centro Elettrotecnico
Sperimentale Italiano S.p.A.
Via Rubattino 54
20134 Milano
Italy


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx CES 10.0011
 
Date of Issue:2010-07-12Issue No.: 0
 
Page 2 of 4
  
Manufacturer:
Pepperl + Fuchs GmbH
Lilienthalstraße 200,
68307 Mannheim
Germany


 
Additional Manufacturing location(s):
Pepperl+Fuchs GmbH (Manufacturing) PTE LTD
18 Ayer Rajah Crescent –
Singapore 139942
Singapore

 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-26 : 2004
Edition: 1
Electrical apparatus for explosve gas atmospheres - Part 26: Construction, test and marking of Group II Zone 0 electrical apparatus
IEC 61241-0 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
IEC 61241-11 : 2005
Edition: 1
Electrical apparatus for use in the presence of combustible dusts - Part 11: Protection by intrinsic safety 'iD'
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:

IT/CES/ExTR10.0011/00


Quality Assessment Report:

DE/PTB/QAR06.0008/02


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx CES 10.0011
 
Date of Issue:2010-07-12Issue No.: 0
 
Page 3 of 4
 
Schedule
 EQUIPMENT:
Equipment and systems covered by this certificate are as follows
 
 

The HiD2025, HiD2025SK, HiD2026 and HiD2026SK devices are associated apparatus for galvanic isolation between hazardous and safety area. They are SMART transmitter power supply repeaters :

- HiD2025 and HiD2025SK are single channel devices

- HiD2026 and HiD2026SK are two channels devices.

The devices provide supply to two wire SMART transmitters located in the hazardous area and repeat the 4 – 20 mA analog values in the safe area as a 4-20mA current source (current sink in HiD202*SK models).

Digital signals (HART protocol) may be superimposed on the analog signal and may be transmitted in both directions.

 

The ambient temperature may vary in a range of -20°C to + 60 °C.



 SPECIFIC CONDITIONS OF USE:   NO
 
 
 


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx CES 10.0011
 
Date of Issue:2010-07-12Issue No.: 0
 
Page 4 of 4
 
 EQUIPMENT(continued):
 
 

Electrical characteristic

The ambient temperature may vary in a range of -20°C to + 60 °C.

 

Not intrinsically safe circuits

Um : 253Vac

Supply rated voltage Un : 24 Vdc

Analog output voltage Un : 30V

 

Intrinsically safe circuits   (SL2 connettor – terminal: CH1: 5a (+) / 5b (-)   ÷   CH2: 1a (+) / 1b (-))

Uo : 26 V                             Ci : negligible

Io : 93 mA                            Li : negligible

Po : 605 mW

 

for gas Group IIC

Co : 0.099 μF                       Lo : 4.1 mH                  Lo/Ro : 58 μH/Ω

for gas Group IIB

Co : 0.77 μF                         Lo : 16.4 mH                Lo/Ro : 235 μH/Ω

for gas Group IIA

Co : 2.6 μF                           Lo : 32.8 mH                Lo/Ro : 470 μH/Ω

 

The capacitance Co and either the inductance Lo or the inductance to resistance ratio (Lo/Ro) of circuits connected to the output terminals of the apparatus must not exceed the above values.

 

Note: The above load parameters apply where:

- the external circuit contains no combined lumped inductance Li and capacitance Ci greater than 1% of the above values;

or

- the inductance and capacitance are distributed as in a cable;

- the external circuit contains either only lumped inductance Li or lumped capacitance Ci in combination with a cable.

 

In all other situations e.g. the external circuit contains combined lumped inductance Li and capacitance Ci, up to 50% of each of the L and C values is allowed.

 
 




Copyright © IEC-IECEx 2019 , Geneva Switzerland. All rights reserved.