IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx CES 10.0017 issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2010-11-02 Page 1 of 3


    
Applicant:
Pepperl+Fuchs GmbH
Lilienthalstraße 200,
68307 - Mannheim
Germany


 
Equipment:Galvanically isolated barrier type HiC2873 and HiC2877
Optional accessory:


 
Type of Protection:Intrinsic Safety "ia"; Dust ignition protection "iD"


 
Marking: [Zone 0] [Ex ia] IIC;
[Ex iaD];
[Ex ia] I
 
Approved for issue on behalf of the IECEx
Certification Body:
Mirko Balaz

 
Position:Head of IECEx CB


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
CESI
Centro Elettrotecnico
Sperimentale Italiano S.p.A.
Via Rubattino 54
20134 Milano
Italy


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx CES 10.0017
 
Date of Issue:2010-11-02Issue No.: 0
 
Page 2 of 3
 
 Manufacturer:
Pepperl+Fuchs GmbH
Lilienthalstraße 200,
68307 - Mannheim
Germany


 
 Additional Manufacturing location(s):
Pepperl+Fuchs (Manufacturing) PTE LTD
18 Ayer Rajah Crescent –
Singapore 139942
Singapore
Pepperl + Fuchs GmbH
Lilienthalstraße 200,
68307 Mannheim
Germany
Germany
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-26 : 2004
Edition: 1
Electrical apparatus for explosve gas atmospheres - Part 26: Construction, test and marking of Group II Zone 0 electrical apparatus
IEC 61241-0 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
IEC 61241-11 : 2005
Edition: 1
Electrical apparatus for use in the presence of combustible dusts - Part 11: Protection by intrinsic safety 'iD'
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
IT/CES/ExTR10.0017/00


Quality Assessment Report:

DE/PTB/QAR06.0007/02DE/PTB/QAR06.0008/02


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx CES 10.0017
 
Date of Issue:2010-11-02Issue No.: 0
 
Page 3 of 3
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

The galvanically isolated barrier types HiC2873 and HiC2877 are Digital-Output repeaters associated apparatus suitable for supplies power to intrinsic safety equipment, such as solenoids, LEDs, and audible alarms placed in a hazardous area, controlled by a Safe Area control signal (in form of switch contact, logic level or loop-powered). They are single channel devices and realize galvanic isolation between hazardous and safety area.

 

The ambient temperature may vary in a range of -20°C to + 60 °C. 

 

See annex for further description.

 
CONDITIONS OF CERTIFICATION: NO
 
 