IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx CES 11.0010 issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2011-04-14 Page 1 of 3


    
Applicant:
Pepperl+Fuchs GmbH
Lilienthalstraße 200,
68307 - Mannheim
Germany


 
Equipment:Galvanically isolated barrier type HiC2025HC and HiC2031HC
Optional accessory:


 
Type of Protection:Intrinsic Safety "ia"; Dust ignition protection "iD"


 
Marking: [Zone 0] [Ex ia] IIC;
[Ex ia] I;
[Ex iaD]
 
Approved for issue on behalf of the IECEx
Certification Body:
Mirko Balaz

 
Position:Head of IECEx CB


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
CESI
Centro Elettrotecnico
Sperimentale Italiano S.p.A.
Via Rubattino 54
20134 Milano
Italy


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx CES 11.0010
 
Date of Issue:2011-04-14Issue No.: 0
 
Page 2 of 3
 
 Manufacturer:
Pepperl+Fuchs GmbH
Lilienthalstraße 200,
68307 - Mannheim
Germany


 
 Additional Manufacturing location(s):
Pepperl+Fuchs (Manufacturing) PTE LTD
18 Ayer Rajah Crescent
– Singapore 139942
Singapore
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-26 : 2006
Edition: 2
Explosive atmospheres - Part 26: Equipment with equipment protection level (EPL) Ga
IEC 61241-0 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
IEC 61241-11 : 2005
Edition: 1
Electrical apparatus for use in the presence of combustible dusts - Part 11: Protection by intrinsic safety 'iD'
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
IT/CES/ExTR11.0011/00


Quality Assessment Report:

DE/PTB/QAR06.0007/02DE/PTB/QAR06.0008/02


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx CES 11.0010
 
Date of Issue:2011-04-14Issue No.: 0
 
Page 3 of 3
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

The intrinsically safe barrier types HiC2025HC e HiC2031HC are galvanically isolated associated apparatus.

The HiC2025HC module provides the supply of two wire (4 ÷ 20mA) intrinsically safe transmitter located in hazardous area and transfer the received signal (4 ÷ 20mA or 1 ÷ 5V) to apparatus placed in the safe area; In addition, the barrier is also able to measure the input signal from active intrinsically safe transmitters.The HiC2031HC module transfers a (4 ÷ 20mA) signal from apparatus placed in safe area to devices placed in hazardous area such as smart I/P converter, electrical valves op positioners.

Both barriers may be superimposed, on the analogue signals, a digital SMART communication signal as input or output and may be transferred in both directions.

 

The ambient temperature may vary in a range of -20°C to + 60 °C.

See annex for further description.

 
CONDITIONS OF CERTIFICATION: NO
 
 