IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx CES 15.0006X issue No.: 0
 
Status:
Current
 
Date of Issue:2015-05-28Page 1 of 3
 
 
Applicant:
Pepperl+Fuchs GmbH
Lilienthalstraße 200,
68307 - Mannheim
Germany
Equipment:Adaptors and Plugs, series AD.RE.., AD.EN.., AD.FF.., AD.MM.., SP.MD...
 
Optional accessory:
 
Type of Protection:Flameproof enclosures ‘d’; increased safety 'e'; Dust ignition protection 't'

 Marking:

Ex d IIC Gb

Ex e IIC Gb

Ex tb III C Db

IP 66/68

 
 
Approved for issue on behalf of the IECEx
Certification Body:
Mirko Balaz

 
Position:Head of IECEx CB


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

  Certificate issued by:
CESI
Centro Elettrotecnico
Sperimentale Italiano S.p.A.
Via Rubattino 54
20134 Milano
Italy


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx CES 15.0006X
 
Date of Issue:2015-05-28Issue No.: 0
 
Page 2 of 3
  
Manufacturer:
Pepperl+Fuchs GmbH
Lilienthalstraße 200,
68307 - Mannheim
Germany


 
Additional Manufacturing location(s):

 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2011
Edition: 6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-1 : 2007-04
Edition: 6
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 60079-31 : 2008
Edition: 1
Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure 't'
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:

IT/CES/ExTR15.0009/00


Quality Assessment Report:

DE/PTB/QAR06.0007/03


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx CES 15.0006X
 
Date of Issue:2015-05-28Issue No.: 0
 
Page 3 of 3
 
Schedule
 EQUIPMENT:
Equipment and systems covered by this certificate are as follows
 
 

The Adaptors series AD.RE.., AD.EN.., AD.FF.. and AD.MM.. are used to match equipments, conduits and hubs having different threaded or plane entry sizes. Attachment of the Adaptors to an enclosure is by means of the male threaded portion on the male body.

The series of available Adaptors are:

  • AD.RE – they are used to reduce a female hub or increase a male hub.
  • AD.EN – they are used to increase a female hub or reduce a male hub.
  • AD.FF – they are used to vary the diameter of a male hub by transforming it into a female hub.
  • AD.MM – they are used to vary the diameter of a female hub by transforming it into a male hub.

The male Plugs series SP.MD.. are suitable for closing female hubs or unused openings on Ex d conduits or Ex d or Ex e enclosures. Attachment of the male plugs to an enclosure is by means of the male threaded portion on the male body.

 

The adaptors and plugs characteristics are further described in the Annexe of this certificate



 SPECIFIC CONDITIONS OF USE:   YES as shown below:
 
 
  • The coupling of the adaptors and plugs with the conduits or enclosures shall be made as indicated by themanufacturer in the documents annexed to this certificate in order respect the type of protection of the electrical apparatus on which the adaptors and plugs are mounted.
  •  The adaptors and plugs shall be mounted at the conduit or at the electrical apparatus in such a way thataccidental rotation and loosening will be prevented.
  •  The adaptors and plugs shall be installed in such a way that the temperature at the mounting point will remain within the following service temperature ranges:
    •  -40°C to +100°C for adaptors and plugs,
    •  Limited up to +80°C for adaptors and plugs supplied with Fiber flat washer.
  •  The degree of protection IP 66/68 according to the IEC 60529 standard will be guaranteed for the adaptors and plugs if the holes into which adaptors and plugs are mounted are suitably sealed. To this scope the correct positioning of the gaskets (for cylindrical threads) or the application of sealant on the threads (for tapered threads), shall be done as indicated in the manufacturer instruction. Therefore it is the users’ responsibility to ensure that the appropriate ingress protection level is maintained.
 




Copyright © IEC-IECEx 2019 , Geneva Switzerland. All rights reserved.