IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx CQM 13.0017 issue No.: 0

Certificate history:

 
Status:
Current
 
Date of Issue:2013-06-18Page 1 of 3
 
 
Applicant:
B&R Ex Systems Pty., Ltd.
Unit 12, 100 Belmore Road, Riverwood NSW 2010 Australia
Australia
Equipment:Explosion-proof controller CSG Series
 
Optional accessory:
 
Type of Protection:Flameproof enclosure "d", Increased safety "e", Protection by enclosure "tD"

 Marking: Ex de IIC T6 / Ex tD A21 IP66 T80 or
Ex e II T6 / Ex tD A21 IP66 T80
-40≤ Ta≤ +40
 
 
Approved for issue on behalf of the IECEx
Certification Body:
Zhang Wei

 
Position:President


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

  Certificate issued by:
China Quality Mark Certification Group Co., Ltd.
No. 33 Zengguang Road, Haidian District,
Beijing City, Postal code: 100037
China


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx CQM 13.0017
 
Date of Issue:2013-06-18Issue No.: 0
 
Page 2 of 3
  
Manufacturer:
B&R Ex Systems Pty., Ltd.
Unit 12, 100 Belmore Road, Riverwood NSW 2010 Australia
Australia


 
Additional Manufacturing location(s):
CZ Explosion-proof Electric Appliances Co., Ltd.
No.1 Qixing Rd, Qixing Town, Nanhu District, Jiaxing, Zhejiang
Post Code: 314002
China

 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-1 : 2003
Edition: 5
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 60079-7 : 2001
Edition: 3
Electrical apparatus for explosive gas atmospheres - Part 7: Increased safety 'e'
IEC 61241-0 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
IEC 61241-1 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 1: Protection by enclosures "tD"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:

CN/CQM/ExTR09.0005/00


Quality Assessment Report:

AU/ITA/QAR10.0007/01CN/CQM/QAR08.0001/02


- PAGE BREAK -

IECEx Certificate
of Conformity

  
Certificate No.:IECEx CQM 13.0017
 
Date of Issue:2013-06-18Issue No.: 0
 
Page 3 of 3
 
Schedule
 EQUIPMENT:
Equipment and systems covered by this certificate are as follows
 
 

Description of equipment

 

The Control Station Series CSG is designed to meet a combined protection technique of Ex d, Ex e and Ex tD.

It comprises of a non metallic cover and base, which houses a combination of IECEx component Certified explosion proof switches and signal modules together with an explosion proof ammeter.

When only the Ammeter is fitted the markings must be Ex e/ Ex tD.

The enclosure is designed to accept certified cable glands, stopping plugs and breathers

Model Types comprise of:

CSG , where equals the enclosure size and are:

 =1 = 95 x 86 x 76,  2 = 135 x 86 x 76, 3 = 175 x 86 x 76,

       5 = 175 x 100 x 76, 6 = 215 x 100 x 76, 51 = 95 x 86 x 76 (illumination switches)

Rating

Max Voltage: 250V

16 amps for switch and signal lamps

15 amps for ammeter circuit
  


 SPECIFIC CONDITIONS OF USE:   NO
 
 
 




Copyright © IEC-IECEx 2019 , Geneva Switzerland. All rights reserved.