IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx CSA 09.0007X issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2009-11-26 Page 1 of 3


    
Applicant:
Pepperl & Fuchs
1600 Enterprise Pkwy.
Twinsburh, OH 44087
United States of America


 
Equipment:6000 Series Purge and Pressurization Control System
Optional accessory:


 
Type of Protection:Ex d [ib] [px] IIC T4 tD A21


 
Marking: Manufacturers name and address
Model Number
Serial Number
Ex d [ib] [px] IIC T4 tD A21 IP6X T60C - For Model 6000 Control Unit
Ex d [ib] [px] IIC T4 tD A21 IP6X T70C - For Model EPV-6000 Vent
-20C ≤ Ta ≤ +50C
 
Approved for issue on behalf of the IECEx
Certification Body:

 
Position:


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
CSA International
178 Rexdale Boulevard
Toronto, Ontario M9W IR3
Canada
and
1707 - 94th Street
Edmonton, AB T6N 1E6
Canada


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx CSA 09.0007X
 
Date of Issue:2009-11-26Issue No.: 0
 
Page 2 of 3
 
 Manufacturer:
Pepperl & Fuchs
1600 Enterprise Pkwy.
Twinsburh, OH 44087
United States of America


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2000
Edition: 3.1
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-1 : 2001
Edition: 4
Electrical apparatus for explosive gas atmospheres - Part 1: Flameproof enclosures 'd'
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-2 : 2001
Edition: 4
Electrical apparatus for explosive gas atmospheres - Part 2: Pressurized enclosures 'p'
IEC 61241-1-1 : 1999
Edition: 2
Electrical apparatus for use in the presence of combustible dust - Part 1-1: Electrical apparatus protected by enclosures and surface temperature limitation - Specification for apparatus
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
CA/CSA/ExTR09.0008/00


Quality Assessment Report:

US/UL/QAR07.0005/02


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx CSA 09.0007X
 
Date of Issue:2009-11-26Issue No.: 0
 
Page 3 of 3
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

Model 6000 Purge Controller with EPV-6000 vent

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 

Cable entries may be used only in places where they are protected against the influence of mechanical danger.

Regularly remove dust from the Control Unit enclosure to prevent excessive temperature rise.

Conduit seals shall be certified in type of explosion protection flameproof “d”, suitable for the conditions of use and correctly installed.

Conduit seals shall be installed within 18 in. of the flameproof “d” enclosure.When the purge control unit is mounted to an enclosure, the complete unit shall be evaluated to EN 60079-2:2004 with Corrigendum April 2006.

The purge control unit has an operating temperature of 135°C (T4 temperature class).  This temperature shall be considered when mounted to an enclosure.

The device must be installed in accordance with the manufacturer’s installation drawing number 116-013UL-12.

 







Copyright © IEC-IECEx 2016 , Geneva Switzerland. All rights reserved.