Certificate No.:
IECEx EXA 13.0003X issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2014-01-31 Page 1 of 3


    
Applicant:
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
Equipment:Input Module “LB1x09*” for Remote I/O-System “LB”
Optional accessory:


 
Type of Protection:Intrinsic Safety “i“, Non Sparking “nA“


 
Marking:

LB1009 * (gas): Ex nA [ic] IIC T4 Gc, or alternatively Ex nAc [ic] IIC T4

LB1109 * (gas): Ex nA [ia Ga] IIC T4 Gc, or alternatively Ex nAc [ia] IIC T4

LB1109 * (dust): [Ex ia Da] IIIC, or alternatively  [Ex ia] IIIC

LB1109 * (mines): [Ex ia Ma] I, or alternatively [Ex ia] I

 
Approved for issue on behalf of the IECEx
Certification Body:
Stipo Đerek

 
Position:Director General


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Agencija za prostore ugrožene eksplozivnom atmosferom (Ex-Agencija)
Bastijanova bb
HR-10001 Zagreb
Croatia
Ex-Agencija_logo_30.jpg


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx EXA 13.0003X
 
Date of Issue:2014-01-31Issue No.: 0
 
Page 2 of 3
 
 Manufacturer:
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
 Additional Manufacturing location(s):
Pepperl + Fuchs PTE Ltd
P + F Building
18 Ayer Rajah Crescent
Singapore 139942
Singapore
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2011
Edition: 6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-11 : 2011
Edition: 6.0
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-15 : 2010
Edition: 4
Explosive atmospheres - Part 15: Equipment protection by type of protection "n"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
HR/EXA/ExTR13.0004/00


Quality Assessment Report:

DE/PTB/QAR06.0007/03DE/PTB/QAR06.0008/05


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx EXA 13.0003X
 
Date of Issue:2014-01-31Issue No.: 0
 
Page 3 of 3
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

The modules LB1x09 * (x = “0” or “1”) are using the same hardware; the difference is in claiming different level of protection for the inputs only. The modules are associated apparatus according to IEC/EN 60079-11 and non-arcing equipment according IEC/EN 60079-15. They can be installed in Zone 2 or safe area. The modules can be operated as 8-channel digital input devices according to Namur Standard (8.2 V supply).

See Annex for other information and electrical parameters. 

 
SPECIFIC CONDITIONS OF USE: YES as shown below:
 

1 1.  The devices must only be used together with the respective backplanes.

12.  Installation in safe area:

The devices must be installed:

-     in an enclosure providing a degree of IP protection at least IP54 according to
  IEC 60529, or

-     in a controlled environment providing pollution degree 2 according to IEC 60664-1.

13. Installation in areas requiring EPL Gc equipment (Zone 2):

     The devices must be installed in an enclosure providing a degree of protection at least IP54 according to IEC 60529 and satisfying the safety requirements for a category EPL Gc enclosure according to IEC 60079-0.

 