IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

leftca_pagelinks
IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx SIR 10.0078 issue No.:0
 
Status:
Current
 
Date of Issue:2010-07-13 Page 1 of 3


    
Applicant:
Walsall Limited
Cornwallis Road
West Bromwich
West Midlands
B70 7DX
United Kingdom


 
Equipment:LCP Range of Enclosures Type ****
Optional accessory:


 
Type of Protection:Increased Safety, Flameproof and Dust


 
Marking: Ex e IIC T6 Gb
Ex e IIC T5 Gb
Ex e d IIC T6 Gb
Ex e d IIC T5 Gb
Ex tb IIIC T85C Db
Ex tb IIIC T100C Db
Ta = -20C, -40C or –45C to +40C, +50C or +55C
 
Approved for issue on behalf of the IECEx
Certification Body:
C Ellaby

 
Position:Certification Officer


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
SIRA Certification Service
Rake Lane
Eccleston
Chester
CH4 9JN
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 10.0078
 
Date of Issue:2010-07-13Issue No.: 0
 
Page 2 of 3
 
 Manufacturer:
Walsall Limited
Cornwallis Road
West Bromwich
West Midlands
B70 7DX
United Kingdom


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2007-10
Edition: 5
Explosive atmospheres - Part 0:Equipment - General requirements
IEC 60079-1 : 2007-04
Edition: 6
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
IEC 60079-31 : 2008
Edition: 1
Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure 't'
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/SIR/ExTR10.0149/00


Quality Assessment Report:

GB/SIR/QAR07.0004/01


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 10.0078
 
Date of Issue:2010-07-13Issue No.: 0
 
Page 3 of 3
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

The type LCP enclosure units use a common moulded base and a range of moulded flat and extension covers; these are made from ‘Menzolit’ type Freemix 43-2101 plastic.  The covers may accept a range of devices such as switch actuators (push button and rotary); alternatively, they are available with instrument viewing windows or can be supplied as a junction box cover.  The covers are secured to the base using equi‑spaced M6 x 16 mm counter bored long hexagonal socket cap head screws.  Up to four, M20 x 1.5 or M25 x 1.5 cable entries, one per side, are provided to accommodate suitably certified cable entry devices and stopping plugs.  The cable entry holes can also be used in conjunction with through bushes assessed as part of this certification when the LCP type enclosures are to be close coupled

 
For a full description refer to the Annexe.
 

The Manufacturer shall comply with the conditions of manufacture listed in the Annexe.

 
CONDITIONS OF CERTIFICATION: NO
 
 