IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx LCI 11.0050X issue No.:1
 
Status:
Current
 
Date of Issue:2011-09-08 Page 1 of 4


    
Applicant:
ABB Inc.
843 N.Jefferson Street
Lewisburg, WV 24901
United States of America


 
Electrical Apparatus:pH/ORP/pION transmitter APA592 and conductivity transmitterACA592
Optional accessory:


 
Type of Protection:Ex ia and Ex iaD


 
Marking: ABB Address: ...
Type: AxA592
Serial number: ... Year of construction: ...
Ex ia IIC T4 Ex iaD 20 IP66 T135°C
Tamb: from -20°C to +60°C
IECEx LCI 11.0050X
Ui = 30V ; Ii = 160mA ; Pi = 0.8W ;
Ci = 5nF ; Li = 0.5mH
Uo = 11.8V ; Io = 5mA ; Po = 15mW ;
Co = 1.45µF ; Lo = 1H
 
Approved for issue on behalf of the IECEx
Certification Body:
Marc GILLAUX

 
Position:Certification Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Laboratoire Central des Industries Electriques (LCIE)
33 Avenue du General Leclerc
FR-92260 Fontenay-aux-Roses
France


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx LCI 11.0050X
 
Date of Issue:2011-09-08Issue No.: 1
 
Page 2 of 4
 
 Manufacturer:
ABB Inc.
843 N.Jefferson Street
Lewisburg, WV 24901
United States of America


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 61241-0 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
IEC 61241-11 : 2005
Edition: 1
Electrical apparatus for use in the presence of combustible dusts - Part 11: Protection by intrinsic safety 'iD'
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
FR/LCI/ExTR11.0051/00


Quality Assessment Report:

NL/KEM/QAR09.0015/01


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx LCI 11.0050X
 
Date of Issue:2011-09-08Issue No.: 1
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

Apparatus APA592 is a pH/ORP/pION transmitter and ACA592 is a conductivity transmitter. They deliver a current in the range 4-20mA proportional to the level detected by sensor. The ambient  temperature range is -20°C to +60°C. Transmitter is supplied by a DC voltage source 30V max. and has a maximum current draw of 23 mA.

Intrinsic safety parameters:

Ui = 30V ; Ii = 160mA ; Pi = 0.8W ;
Ci = 5nF ; Li = 0.5mH
Uo = 11.8V ; Io = 5mA ; Po = 15mW ;
Co = 1.45µF ; Lo = 1H

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 

Ambient temperature range: from -20°C to +60°C.

The apparatus shall only be connected to an intrinsically safe certified equipment (see electrical parameters above). This combination must be compatible as regard the intrinsic safety rules.

 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx LCI 11.0050X
 
Date of Issue:2011-09-08Issue No.: 1
 
Page 4 of 4
 
 
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 
Issue 1: correction of presentation.
 
 








Copyright © IEC-IECEx 2013 , Geneva Switzerland. All rights reserved.