IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BAS 12.0059X issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2012-04-12 Page 1 of 4


    
Applicant:
Toshiba Mitsubishi - Electric Industrial Systems Corporation
2-4 Suehiro-cho
Tsurumi-ku
Yokohama
230-0045
Japan


 
Electrical Apparatus:A 3350kW, 6.6kV, 3 phase, 4 pole, 50 Hz Water Cooled Purged and Pressurised Motor
Optional accessory:


 
Type of Protection:Pressurisation and Increased Safety


 
Marking:

Ex e px IIC T3 Gb

 
Approved for issue on behalf of the IECEx
Certification Body:
R S Sinclair

 
Position:General Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Baseefa
Rockhead Business Park
Staden Lane
Buxton
Derbyshire
SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 12.0059X
 
Date of Issue:2012-04-12Issue No.: 0
 
Page 2 of 4
 
 Manufacturer:
Toshiba Mitsubishi - Electric Industrial Systems Corporation
2-4 Suehiro-cho
Tsurumi-ku
Yokohama
230-0045
Japan


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2007-10
Edition: 5
Explosive atmospheres - Part 0:Equipment - General requirements
IEC 60079-2 : 2007-02
Edition: 5
Explosive Atmospheres - Part 2 Equipment protection by pressurized enclosure "p"
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/BAS/ExTR12.0099/00


Quality Assessment Report:

GB/BAS/QAR06.0021/03


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 12.0059X
 
Date of Issue:2012-04-12Issue No.: 0
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 
A 3350kW, 6.6kV, 3 phase, 4 pole, 50 Hz Water Cooled Synchronous Purged and Pressurised Motor comprises a fabricated steel motor casing employing a closed internal cooling air circuit, which is cooled using a fabricated steel water to air heat exchanger mounted adjacent to the motor housing.

An internal fan is attached at each end of the rotor for the circulation of the internal air around the windings and through the heat exchanger. 

The rotor is supported by frame mounted bearings at both ends. 

At the non-drive end there is an exciter housing.

The motor and cooler assembly, the main and neutral point terminal boxes and the exciter housing are designed to be purged and pressurised by an Expo Minipurge Leakage Compensation Control System. The assembly is provided with an inlet for the pressurisation and purging air and pipe work forming an air distribution system. A flow monitoring and spark arresting device is provided for the exit of the purging and pressurising air.

The low pressure monitoring port is situated in front of the internal fan at the drive end. Metal pipe work connects this to the low pressure switch within the pressurisation and purging control system.

The motor and exciter are fitted with increased safety heaters to IECEx BAS06.0081U. Increased safety terminal boxes to IECEx BAS 08.0021U are provided for the connection of these heaters and also for the connection of internal air and bearing resistance temperature detectors (RTDs). 

See Annex for full details.

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 
1. The enclosures are purged with air at a flow rate of not less than 3000 l/min (3 m3/min) through the outlet for a period of not less than 45 minutes.

2. Each and every machine is to be subjected to an internal overpressure test of 52.5 mbar for two minutes, followed by a leakage test at 35 mbar. The leakage shall not exceed 1000 l/min (1 m3/min).

3. The pressurisation and purging system attached to the enclosures must be:-

a. Set to provide the above purge flow rate and time
b. Set to provide a low pressure monitoring system set to a minimum of 4 mbar.

Continued on Page 4.
 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 12.0059X
 
Date of Issue:2012-04-12Issue No.: 0
 
Page 4 of 4
 
 
Additional information:
 

Conditions of Certification continued

4. The pressurisation and purging system attached to the enclosures shall be subjected to a test to demonstrate effective operation under the following conditions:-

a.  Underpressure - The low pressure switch is to operate if the enclosure overpressure falls below the minimum specified above (e.g. if an inspection panel is opened).

b.  Purge flow failure - The purging system (including the timer) is to reset to the beginning of the purge cycle if the purging air flow rate (measured at the outlet) falls below the minimum specified above (e.g. the supply restricted during purge).

c.  Supply pressure failure -The low pressure switch is to operate when or before the enclosure overpressure falls below the minimum specified above (e.g. the supply restricted after purge).

5. For correct operation the on-site pressurising air supply must be capable of providing a minimum of 500 l/min (0.5 m3/min)  for leakage compensation.

6.  The heating element supply circuit is to be interlocked such that the heaters cannot be energised whilst the motor is running, and this supply circuit is to include a suitable protection device as detailed in IEC 60079-7.

7.  The resistance temperature detectors included in the stator windings on this machine are to be separately protected (i.e. by connection to an intrinsic safety circuit), or automatically disconnected in the event of a purge/pressurisation failure.

8.  Precautions shall be taken to guard against danger from high temperature and voltage in the secondary circuit of the current transformers in the event that the secondary circuit, external to the pressurised enclosure, becomes open-circuit.

9.  This motor is supplied with bearing insulation, the user is responsible for checking the effectiveness of such installations at appropriate intervals, e.g. by the use of a 100V insulation tester and by visual inspection to ensure that no unpainted, unearthed metal can be shorted to earth.

10.  The minimum specified cooling water flow rate is 440 l/min at a maximum temperature of 33°C.

11.  The attention of the user is drawn to the need to ensure that certified ancillaries are appropriate for the conditions of use and are interconnected in accordance with IEC 60079-14.  The Conditions of Certification, or Schedule of Limitations as appropriate for individually certified units (equipment or component), remain applicable to the units fitted to this motor. 

 

 
 