IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx BAS 11.0076X issue No.:1
 
Status:
Current
 
Date of Issue:2012-04-13 Page 1 of 4


    
Applicant:
Hawke International
A Division of Hubbell Limited
A Member of the Hubbell Group of Companies
Oxford Street West
Ashton-under-Lyne
Lancashire
OL7 0NA
United Kingdom


 
Electrical Apparatus:489 Flameproof Breather Drain
Optional accessory:


 
Type of Protection:Flameproof


 
Marking: Ex d I Mb
Ex d IIB+H2 T6 Gb Tamb (-60°C to +60°C)
 
Approved for issue on behalf of the IECEx
Certification Body:
R S Sinclair

 
Position:General Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Baseefa
Rockhead Business Park
Staden Lane
Buxton
Derbyshire
SK17 9RZ
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 11.0076X
 
Date of Issue:2012-04-13Issue No.: 1
 
Page 2 of 4
 
 Manufacturer:
Hawke International
A Division of Hubbell Limited
A Member of the Hubbell Group of Companies
Oxford Street West
Ashton-under-Lyne
Lancashire
OL7 0NA
United Kingdom


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2007-10
Edition: 5
Explosive atmospheres - Part 0:Equipment - General requirements
IEC 60079-1 : 2007-04
Edition: 6
Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
GB/BAS/ExTR11.0169/00GB/BAS/ExTR12.0096/00


Quality Assessment Report:

GB/BAS/QAR06.0061/03


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 11.0076X
 
Date of Issue:2012-04-13Issue No.: 1
 
Page 3 of 4
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 
The Type 489 Breather Drain is designed to be fitted into the bottom face a flameproof enclosure to allow the enclosure to breathe and drain.

There are 2 sizes: M20 x 1.5mm pitch and M25 x 1.5mm pitch or non metric equivalents as defined in the certification documentation.

The breather drain comprises a brass, steel or stainless steel body with a hexagonal head and a threaded portion 15mm long minimum which forms a threaded flameproof joint with enclosure. In the bore of the body there is a press fit bronze sinter. The hexagonal head of the breather drain has drain holes passing behind the sinter. For these parallel thread versions a nitrile rubber or silicone rubber o-ring set in a groove in the shoulder of the thread ensures efficient sealing onto an associated enclosure.

The breather drain, when fitted in the bottom face of the equipment, is capable of meeting the requirements of IP66

Variation 0.1

The metric male threads may be replaced by 1/2” NPT and 3/4” NPT respectively.

 

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 
1. The breather drain is to be mounted in the bottom face of the enclosure to ensure it is able to breathe and drain effectively when IP66 ingress protection is required.

2. The maximum free volume of the enclosure into which the breather may be fitted is 2.5litres unless tested in accordance with Clause 10 of IEC 60079-1 in the larger enclosure.

3. Only one breather drain shall be fitted into any single flameproof enclosure.

4. The breather drain thread is to be secured in the enclosure with Loctite 638 sealant or a direct equivalent.

 

 


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx BAS 11.0076X
 
Date of Issue:2012-04-13Issue No.: 1
 
Page 4 of 4
 
 
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
 
Variation 1.1

Clarification of Sinter details to aid production
  

 ExTR:  GB/BAS/ExTR12.0096/00

File Reference:   12/0323
  

 

 
 








Copyright © IEC-IECEx 2013 , Geneva Switzerland. All rights reserved.