IECEx CoC Home > Certified Equipment Scheme > Certificate of Conformity
important information !
an IECEx Guest User | ExCB Login

IECEx Certificate
of Conformity

 
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

 
Certificate No.:
IECEx SIR 05.0057X issue No.:0

Certificate history:

 
Status:
Current
 
Date of Issue:2008-09-30 Page 1 of 3


    
Applicant:
Pratley Manufacturing and Engineering (pty) Ltd
Jackson Street
Factoria
Krugersdorp
South Africa


 
Electrical Apparatus:Envirogland and Enviro Compression Glands
Optional accessory:


 
Type of Protection:Increased Safety and Dust


 
Marking: Ex e II
Ex tD A21 IP68
 
Approved for issue on behalf of the IECEx
Certification Body:
D R Stubbings BA MIET

 
Position:Certification Manager


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
SIRA Certification Service
Rake Lane
Eccleston
Chester
CH4 9JN
United Kingdom


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 05.0057X
 
Date of Issue:2008-09-30Issue No.: 0
 
Page 2 of 3
 
 Manufacturer:
Pratley Manufacturing and Engineering (pty) Ltd
Jackson Street
Factoria
Krugersdorp
South Africa


 
 Additional Manufacturing location(s):
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-7 : 2006-07
Edition: 4
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
IEC 61241-0 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
IEC 61241-1 : 2004
Edition: 1
Electrical apparatus for use in the presence of combustible dust - Part 1: Protection by enclosures "tD"
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
IECEx ATR:File Reference:
GB/SIR/ExTR08.0118/00   51F13361  
GB/SIR/QAR06.0042/00    
   


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx SIR 05.0057X
 
Date of Issue:2008-09-30Issue No.: 0
 
Page 3 of 3
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

The Enviro Compression gland range is manufactured in glass filled polyamide and brass. They are intended to terminate braided or unarmoured circular cables into increased safety enclosures without compromising the explosion protection provided by the enclosures in accordance with relevant codes of practice, with sealing and retention provided by gripping the outer sheath

 
The cable gland range has an ingress protection rating of IP68

 

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 

1

The Enviro Compression Gland, Envirogland  and Pb Envirogland ranges shall not be used in enclosures where the temperature, at the point of mounting, is outside the range of -20°C to +60°C
2The Enviro Compression Gland, Envirogland  and Pb Envirogland ranges are susceptible to electrostatic discharge. As such the installation instruction leaflet carries a precautionary warning to minimise the risk
 







Copyright © IEC-IECEx 2016 , Geneva Switzerland. All rights reserved.