Date of Issue:2009-11-03 Page 1 of 3


    
Applicant:
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
Equipment:Ethernet Isolator type EI-0D2-10Y-10B***
Optional accessory:


 
Type of Protection:General requirements, Intrinsic Safety, type "n"


 
Marking: [Ex ia] IIB
resp.
Ex nA [ia IIB] II T4
resp.
[Ex ia] I
 
Approved for issue on behalf of the IECEx
Certification Body:
Dr.-Ing. U. Johannsmeyer

 
Position:Head of Department "Intrinsic Safety and Safety of Systems"


 
Signature:
(for printed version)
 
Date:
 
 
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
 

 Certificate issued by:
Physikalisch-Technische Bundesanstalt (PTB)
Bundesallee 100
38116 Braunschweig
Germany


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx PTB 09.0053X
 
Date of Issue:2009-11-03Issue No.: 0
 
Page 2 of 3
 
 Manufacturer:
Pepperl + Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim
Germany


 
 Additional Manufacturing location(s):
Pepperl + Fuchs (Manufacturing) PTE LTD
18 Ayer Rajah Crescent
Singapore 139942
Singapore
 

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.


STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

 
IEC 60079-0 : 2004
Edition: 4.0
Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
IEC 60079-11 : 2006
Edition: 5
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-15 : 2005-03
Edition: 3
Electrical apparatus for explosive gas atmospheres Part 15: Construction, test and Marking of Type of Protection "n" electrical apparatus
 
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the Standards listed above.


 
TEST & ASSESSMENT REPORTS:A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

 
Test Report:
DE/PTB/ExTR09.0060/00


Quality Assessment Report:

DE/PTB/QAR06.0007/02DE/PTB/QAR06.0008/01


- PAGE BREAK -

IECEx Certificate
of Conformity

 
Certificate No.:IECEx PTB 09.0053X
 
Date of Issue:2009-11-03Issue No.: 0
 
Page 3 of 3
 
 
Schedule
 
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
 

The Ethernet Isolator, type EI-0D2-10Y-10B*** is used to generate a galvanically isolated, intrinsically safe Ethernet signal (Ex ia IIB) from a non-intrinsically safe Ethernet signal.

The equipment is intended for application as associated apparatus outside the hazardous area and as zone 2 equipment using the identical design.The permissible range of the ambient temperature is  -40 °C up to +60 °C.

 
CONDITIONS OF CERTIFICATION: YES as shown below:
 
1. For the application as zone 2 equipment the Ethernet Isolator, type EI-0D2-10Y-10B***  shall be installed into a housing which fulfills a minimum degree of protection of IP 54  according to IEC 60529:1989 + A1:1999.

2.  In an ambient temperature range from -40 °C to -25 °C the ethernet interface contacts  (RJ45) of the Ethernet Isolator, type EI-0D2-10Y-10B*** must not be plugged or un-plugged or mechanically stressed in any other way.
 







Copyright © IEC-IECEx 2016 , Geneva Switzerland. All rights reserved.